TC10EM
P. 19 / 43
EM-9581-B Rev.1
5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201 Fax: +81(6)6659-8510 E-mail: [email protected]
■
REMOTE SP
Input 2 signal can be cascaded into Input 1 setpoint value as Remote SP.
ADDRESS
PARAMETER
RANGE
DEFAULT
197
Loop 1, Remote SP
0 : Disable
1 : Enable
0
Remote SP operates as in the function diagram below.
Local and remote SP are switched by an event input. If no event input is assigned, only the remote SP is used.
■
SP TRACKING
Specify whether the remote SP should be carried on when it is switched to the local SP mode.
ADDRESS
PARAMETER
RANGE
DEFAULT
198
Loop 1, SP tracking
0 : Disable
1 : Enable
0
■
SP LOW LIMIT / SP HIGH LIMIT
Specify the lower and the upper limits for the SP.
For example, if the SP range is set to 0.0
−
100.0, setting 100.0 is used for setting 200.0 automatically.
ADDRESS
PARAMETER
RANGE
DEFAULT
199
Loop 1, SP low limit
-3200.0 to +3200.0
(decimal by input 1 decimal setting)
-3200.0
200
Loop 1, SP high limit
3200.0
455
Loop 2, SP low limit
-3200.0 to +3200.0
(decimal by input 2 decimal setting)
-3200.0
456
Loop 2, SP high limit
3200.0
Input 1
Loop 1
Selected Bank SP
Local SP
Input 2
Loop 2
Selected Bank SP
Local SP
Internal SP
Event Input
Remote SP
Remote SP
Internal SP
Loop 1 Control
PV
Loop 2 Control
PV