UNIVERSAL INPUT
The Controller has two universal inputs (universal input 1, universal input 2) which can be assigned independently for tem-
perature inputs. In addition to RTD and thermocouples, resistor, DC and potentiometer inputs are also usable. The resistor,
DC and potentiometer input is scaled into a temperature range.
Universal input 1 is usually assigned as PV input signal for loop 1, while universal input 2 is for loop 2. Universal input 2
signal can be cascaded into the loop 1 SP.
■
INPUT TYPE
ADDRESS
PARAMETER
RANGE
DEFAULT
129
Universal input 1, Input type
See the table below.
10
385
Universal input 2, Input type
• DC Voltage (-10 – +10V DC)
• DC Current (0 – 20mA DC)
CJC
SENSOR
+
––
INPUT
• DC Voltage (-1000 – +1000mV DC)
INPUT
• Thermocouple
• RTD / Resistor (3-wire)
Universal Input 1
• Potentiometer
comp. leadwire
A
B
B
• RTD / Resistor (2-wire)
A
B
MAX
MIN
Universal Input 2
Loop 1
Loop 2
SET VALUE
PARAMETER
0
DC 0
−
20mA
1
DC -1000
−
+1000mV
2
DC -10
−
+10V
3
POT 0
−
4000Ω
4
POT 0
−
2500Ω
5
POT 0
−
1200Ω
6
POT 0
−
600Ω
7
POT 0
−
300Ω
8
POT 0
−
150Ω
9
Resistor 0
−
4000Ω
10
RTD Pt 100
14
RTD Pt 500
15
RTD Pt 1000
16
RTD Pt 50Ω
17
RTD JPt 100
SET VALUE
PARAMETER
20
RTD Ni 508.4Ω
22
RTD Cu 10
24
TC (PR)
25
TC K
26
TC E
27
TC J
28
TC T
29
TC B
30
TC R
31
TC S
32
TC C
33
TC N
34
TC U
35
TC L
36
TC P