TC10EM
P. 21 / 43
EM-9581-B Rev.1
5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201 Fax: +81(6)6659-8510 E-mail: [email protected]
■
PV ALARM 1, PV ALARM 2, PV ALARM 3
The Controller monitors PV signal to trigger alarms in predefined conditions.
Three alarm conditions (PV ALARM 1 through 3) per loop can be specified.
High/low setpoint values can be specified by banks, together with other settings such as SP.
• ALARM TYPE
Specify conditions to be monitored for alarm trip.
ADDRESS
PARAMETER
RANGE
DEFAULT
321
Loop 1, Alarm 1 type
See the table below.
0
329
Loop 1, Alarm 2 type
337
Loop 1, Alarm 3 type
577
Loop 2, Alarm 1 type
585
Loop 2, Alarm 2 type
593
Loop 2, Alarm 3 type
Standby sequence is a function to prevent unwanted alarm triggered at the startup or at an SP change. If the PV is in alarm
range at the startup or at an SP change, no alarm is triggered until the PV is out of the range. Once it is out and then in the
range again, normal alarm function starts functioning.
SET VALUE
0
Alarm OFF
1
Deviation Hi/Lo limit
2
Deviation Hi limit
3
Deviation Lo limit
4
Deviation range
5
Deviation Hi/Lo limit
with standby sequence
6
Deviation Hi limit
with standby sequence
7
Deviation Lo limit
with standby sequence
8
Absolute value Hi/Lo limit
9
Absolute value Hi limit
10
Absolute value Lo limit
11
Absolute value Hi/Lo limit
with standby sequence
12
Absolute value Hi limit
with standby sequence
13
Absolute value Lo limit
with standby sequence
alarm range
Lo
SP
Hi
SP
Hi
Lo
SP
Lo
SP
Hi
Lo
SP
Hi
SP
Hi
Lo
SP
Lo
0
0
Hi
Hi
Lo
0
Lo
0
Hi
Lo
0
Hi
0
ALARM TYPE