When Normal plotting is selected, the plot area is divided equally. When Logarithmic is selected, the plot area is
divided in specified scale of exponents of 10.
For Logarithmic plotting, specify the lower limit of exponent in ‘Logarithmic Plot Position Exponent’ field within -9 to
8, and how many divisions you wish to have in ‘Exponential Scale’ among 10, 5, 4, 2, and 1.
Square Root
Input data is square-root-extracted when this setting is enabled.
Overview Color
Specify the bargraph color for the pen in the Overview. Use the color palette.
MODEL
I/O TYPE
SELECTIONS
USABLE AND MEASURABLE RANGE
°C
°F
R3-TS4
R3-TS8
T/C input
(PR)
0 – 1760
-62 – 3200
K (CA)
-270 – 1370
-454 – 2498
E (CRC)
-270 – 1000
-454 – 1832
J (IC)
-210 – 1200
-346 – 2192
T (CC)
-270 – 400
-454 – 752
B (RH)
100 – 1820
212 – 3308
R
-50 – 1768
-58 – 3214
S
-50 – 1768
-58 – 3214
C (WRe 5-26)
0 – 2315
32 – 4199
N
-270 – 1300
-454 – 2372
U
-200 – 600
-328 – 1112
L
-200 – 900
-328 – 1652
P (Platinel II)
0 – 1395
32 – 2543
R3-RS4
R3(Y)-RS8
RTD input
Pt 100 (JIS ’97/IEC)
-200 – 850
-328 – 1562
Pt 100 (JIS ’89)
-200 – 660
-328 – 1220
JPt 100 (JIS ’89)
-200 – 510
-328 – 950
Pt 50Ω (JIS ’81)
-200 – 649
-328 – 1200
Ni 100
-80 – 250
-112 – 482
Cu 10
-50 – 250
-58 – 482
Pt 1000*
-200 – 850
-328 – 1562
Ni 508.4*
-50 – 200
-58 – 392
Cu 50
-50 – 150
-58 – 302
Ni 1000*
-56 – 152
-68 – 305
*Not usable with the R3-RS8.