47DT OPERATING MANUAL EM-9508-B Rev.7
9.2 ANALOG OUTPUT FUNCTION MODE
9.2.1 OPERATING PROCEDURE
NOTE
The following figures are display examples. The displays
depend on the settings.
1
Hold down Init/
↑
button for 3 seconds or more to move on to
Initial Setting Mode.
• The input type is indicated.
• The SD indicates ‘TCTYPE’.
2
Press Alarm/
↓
or Init/
↑
button to go to the analog output func-
tion mode setting.
• The analog output function mode is indicated.
• The SD indicates ‘ANG VAL’.
3
Press Shift and Up buttons to select the analog output func-
tion mode.
• Select ‘DISPLY’ or ‘TEMP’.
4
Press Alarm/
↓
or Init/
↑
button to apply the new setting.
• And the next parameter setting is indicated.
NOTE
• Press Alarm/
↓
button, and the analog output 0% will be indicated (‘ANG L’ on the SD).
• Press Init/
↑
button, and the analog output type will be indicated (‘ANG TYP’ on the SD)..
2,4
1,2,
4
3
3
Blinking