12.1 P OUTPUT
Alarm outputs are normally assigned to the LL, L, H and HH alarms and there is not an output for the P status. However
the P output can be assigned to an output instead of one of them. The default setting is “no P output”.
NOTE
• When the P output is assigned, the ON delay time, OFF delay time, one-shot output and coil at alarm of the assigned
alarm point operate according to each setting of the P status.
• The operation of the alarm indicators are not changed even when the P output is set.
12.1.1 OPERATING PROCEDURE
NOTE
The following figures are display examples. The displays
depend on the specifications and settings.
1
Hold down Alarm/
↓
and Init/
↑
buttons at once for 3 seconds or
more to move on to Advanced Setting Mode.
• The averaging type is indicated.
• The SD indicates ‘AVE-TP’.
NOTE
With the I/O option code ‘6’ or ‘A’, the event trigger mode is indicated (‘EVENT’ on the SD).
2
Press Alarm/
↓
or Init/
↑
button to go to the P output setting.
• The P output is indicated.
• The SD indicates ‘PASS’.