1.7.9 WIRING NETWORK INTERFACE
Writing/reading each measured value and configurations is available with a PC or PLC via
Modbus communication.
Transmission
Half-duplex, asynchronous, no procedure
Interface
Conforms to TIA/EIA-485-A
Max. transmission distance
500 meters
Baud rate
1200, 2400, 4800, 9600, 19200, 38400 bps
Protocol
Modbus-RTU
Node address
1 to 247
Max. number of nodes
31 (except the master)
Media
Shielded twisted-pair cable (CPEV-S 0.9 dia.)
IMPORTANT
• Internal terminating resistor is used when the device is at the end of a transmission line.
• Install shield cables to all sections and ground them at single point for noise protection.
• Connect in a daisy chain.
• Be sure to confirm the polarity in wiring.
• Use duplex or triplex shield cables.