background image

035-14527-000 REV A (599)

Form 650.77-N3U

Unitary Products Group

13

SUPPLY AIR DUCTS

Installations on combustible material or floors must use a
combustible floor base (Refer to Figure 9 on page13)
(1CB0314, 17, 21 & 24) as specified on the rating plate or a
matching cooling coil. Follow the instructions supplied with
the combustible floor base accessory.

This base can be replaced with a matching cooling coil, prop-
erly sealed to prevent leaks. Follow the cooling coil instruc-
tions on page23 for installing the plenum.

GAS PIPING

NOTE: 

An accessible manual shutoff valve must be installed

upstream of the furnace gas controls and within 6 feet of the
furnace.

The furnace and its individual shutoff valve must be discon-
nected from the gas supply piping system during any pres-
sure testing of that system at test pressures in excess of 1/2
psig (3.48 kPa).

The furnace must be isolated from the gas supply piping sys-
tem by closing its individual external manual shutoff valve
during any pressure testing of the gas supply piping system
at test pressures equal to or less than 1/2 psig (3.48 kPa).

Gas piping may be connected from either side of the furnace.
Sizing and installation of the supply gas line should comply
with the local utility requirements.

The gas supply should be a separate line, installed in accor-
dance with the National Fuel Gas Code, ANSI Z223.1, or
CAN/CGA B149.1 or.2 Installation Codes - (latest editions). 

Some utility companies, or local codes, require pipe sizes
larger than the minimum sizes listed. Using the properly sized
wrought iron, approved flexible or steel pipe, make gas con-

 FIGURE 8 :  DOWNFLOW FILTERS

 FIGURE 9 :  COMBUSTIBLE FLOOR BASE 

ACCESS’Y

An overpressure protection device, such as a
pressure regulator, which conforms to the National
Fuel Gas Code, ANSI Z223.1 (U.S.) or CAN-
B149.1 or.2 (Canada) and acts to limit the down-
stream pressure to value that does not exceed 0.5
PSI (14" w.c.), must be installed in the gas piping
system upstream of the furnace. Failure to do so
may result in a fire or explosion or cause damage
to the furnace or some of its components.

Never apply a pipe wrench to the body of the com-
bination automatic gas valve. A wrench must be
placed on the projection or wrench boss of the
valve when installing piping to it.

Содержание P*DD & G8D-DN series

Страница 1: ...MID EFFICIENCY GAS FIRED TUBULAR HEAT EXCHANGER SERIES MODELS P DU G8D UH Upflow Horizontal P DD G8D DN Downflow 57 120 MBH INPUT 035 14527 000 REV A 599 Form 650 77 N3U FOR YOUR SAFETY WHAT TO DO IF...

Страница 2: ...ds 4 Paper bags boxes or other paper products Never operate the furnace with the blower door removed To do so could result in serious personal injury and or equipment damage CONTENTS GENERAL INFORMATI...

Страница 3: ...arify or make the installation easier CAUTIONS are given to prevent equipment damage WARNINGS are given to alert the installer that personal injury and or equipment or property damage may occur if ins...

Страница 4: ...appliance when access is required for servicing and cleaning Eighteen 18 inches at the side where access is required for passage to the front when servicing or for inspection or replacement of flue ve...

Страница 5: ...of all appliances located in the space NOTE Ducts must have the same cross sectional area as the free area in the opening to which they are connected The minimum dimension of rectangular ducts shall b...

Страница 6: ...inting inks paint removers varnishes etc o Hydrochloric acids p Cements and glues q Antistatic fabric softeners for clothes dryers r Masonry acid washing chemicals VENTING CATEGORY I VERTICAL VENTING...

Страница 7: ...0 53 2000 C 21 80 25 55 30 60 160 1 11 x 10 12 0 20 14 145 120 78 96 64 1600 C 21 80 25 55 45 75 180 1 2 10 x 10 12 0 20 14 145 120 78 96 64 2000 C 21 80 25 55 35 65 170 1 11 x 10 12 0 20 14 147 1 AFU...

Страница 8: ...11 x 10 12 0 20 14 130 100 65 80 52 1200 B 17 1 2 80 25 55 40 70 170 1 2 10 x 8 12 0 20 14 125 120 78 96 64 2000 C 21 80 25 55 30 60 160 1 11 x 10 12 0 20 14 150 1 AFUE numbers are determined in accor...

Страница 9: ...rrections or resizing of the common venting sys tem must be in accordance with the National Fuel Gas Code ANSI Z223 1 or Section 7 Venting Systems and Air Supply for Appliances CAN CGA B149 1 or 2 Ins...

Страница 10: ...eld installation Internal Installation 1 Select desired filter position left right side or bottom Remove the corresponding cabinet cut outs per instruc tions provided 2 Install snap in retainer clips...

Страница 11: ...m structure is suitable to support the weight of the furnace Refer to Figure 3 on page10 for unit dimensions and Refer to Table3 on page7 for unit weights Be sure to seal the furnace to plenum connect...

Страница 12: ...ort at return air end of unit Units may also be suspended by using straps or other mate rial at the same location All four suspension points must be level to ensure quiet furnace operation DOWNFLOW MO...

Страница 13: ...m at test pressures equal to or less than 1 2 psig 3 48 kPa Gas piping may be connected from either side of the furnace Sizing and installation of the supply gas line should comply with the local util...

Страница 14: ...e the screw retaining the wiring box Route the power wiring through the unit side panel with a conduit connector or other proper connection Make wiring connections as shown in Figure 11 or 12 Replace...

Страница 15: ...the cabinet NOTE Some electronic thermostats do not have adjustable heat anticipators They may have other type cycle rate FIGURE 11 UPFLOW MODELS P DU G8D UH ELECTRICAL WIRING FIGURE 12 DOWNFLOW MODE...

Страница 16: ...gh temperature limit control is located on the furnace vestibule panel just to the right and above the gas valve This is an automatic reset control and provides over temperature protection due to redu...

Страница 17: ...n off all other gas appliances connected to gas meter 2 With the furnace turned on measure the time needed for one revolution of the hand on the smallest dial on the meter A typical domestic gas meter...

Страница 18: ...screw counter clockwise Adjust regulator until pressure shown on manometer matches the pressure specified on the appli ance rating plate 6 Replace low adjustment seal screw and tighten securely Cycle...

Страница 19: ...g label and Figure 16 on page19 You may select a heating speed and a cooling speed They may be the same speed or a different speed To use the same speed tap for heating and cooling the heat terminal a...

Страница 20: ...aner Connection Two 1 4 spade terminals EAC and EAC N for electronic air cleaner connections are located on the control board The terminals provide 115 VAC 1 0 amp maximum during circu lating blower o...

Страница 21: ...1443 1353 1270 1137 993 800 LOW 1377 1297 1284 1271 1246 1194 1125 1005 851 727 120 96 1600 C HIGH 1927 1855 1780 1693 1611 1503 1382 1224 1039 833 MED 1649 1608 1556 1502 1423 1342 1218 1075 910 723...

Страница 22: ...64 964 851 725 594 LOW 1024 1018 1002 970 930 882 798 722 622 508 80 64 1600 B HIGH 2047 1992 1911 1842 1780 1688 1607 1513 1412 1284 MED 1862 1826 1764 1698 1629 1558 1496 1408 1310 1177 LOW 1673 165...

Страница 23: ...is satisfied the inducer motor is reduced to low speed and the second stage gas valve is de energized upon opening of the second stage pressure switch contacts The circulator remains on high heat spee...

Страница 24: ...reinstalling the filter be sure the filter completely covers the cabinet opening and is secured in place by the wire retainer Downflow Installations 1 Turn off electrical power supply to the furnace a...

Страница 25: ...e orientation of the burner flanged side down before removing Burners may be cleaned by rinsing in hot water or by using a vacuum cleaner CLEANING THE HEAT EXCHANGER Lower Heat Exchanger Access 1 Turn...

Страница 26: ...INUOUS FLASHING 1 sec on 1 sec off This indi cates that flame was sensed when there was not a call for heat With this fault code the control will also turn on both the inducer motor and supply air blo...

Страница 27: ...r faulty gas valve LED ON CONSTANTLY This indicated an internal fault in the furnace control discovered during its self check proce dure Replace the control 60 MINUTE AUTOMATIC RESET FROM LOCKOUT This...

Страница 28: ...ELECTRICAL 1NP0480 Propane Conversion Kit 1SR0302 External Side Filter Rack 6 Pack 1BR0314 External Bottom Filter Rack Cabinet A 1BR0317 External Bottom Filter Rack Cabinet B 1BR0321 External Bottom F...

Страница 29: ...035 14527 000 REV A 599 Form 650 77 N3U Unitary Products Group 29 FIGURE 18 SEQUENCE OF OPERATION...

Страница 30: ...035 14527 000 REV A 599 Form 650 77 N3U 30 Unitary Products Group WIRING DIAGRAM UPFLOW HORIZONTAL MODELS P DD G8D UH NOTE The furnace s control system depends on correct polarity of the power supply...

Страница 31: ...035 14527 000 REV A 599 Form 650 77 N3U Unitary Products Group 31 WIRING DIAGRAM DOWNFLOW MODELS P DD G8D DN NOTE The furnace s control system depends on correct polarity of the power supply...

Страница 32: ...hange without notice Printed in U S A Copyright by Unitary Products Group 1999 All rights reserved Supersedes 650 77 N2U 1198 650 77 N3U 599 Unitary 5005 Interstate Norman Product Drive OK Group North...

Отзывы: