LION I/O Modules
▪
Digital Outputs
59
10.3.2
Configuration Data – Filter Constant
The filter constant defines the time lag of the data capture of input signals. For
setting the time lag, one bit per byte has to be set to 1, all other bits in the byte
must be 0. Following time lags can be set:
▪ 1 ms
▪ 2 ms (Default)
▪ 5 ms
▪ 10 ms
▪ 20 ms
Data Structure
68
KON
0 or 1 (configuration data)
69
–
–
70
–
–
71
–
–
If no time is set, the default value of 2 ms is set automatically.
Bit
Channel
Content
0
1 (Potential A)
1 ms
1
1 (Potential A)
2 ms
2
1 (Potential A)
5 ms
3
1 (Potential A)
10 ms
4
1 (Potential A)
20 ms
5 – 7
1 (Potential A)
–
8
2 (Potential B)
1 ms
9
2 (Potential B)
2 ms
10
2 (Potential B)
5 ms
11
2 (Potential B)
10 ms
12
2 (Potential B)
20 ms
13 – 15
2 (Potential B)
–
16
3 (Potential C)
1 ms
17
3 (Potential C)
2 ms
18
3 (Potential C)
5 ms
19
3 (Potential C)
10 ms
20
3 (Potential C)
20 ms
21 – 23
3 (Potential C)
–
24
4 (Potential D)
1 ms
25
4 (Potential D)
2 ms
26
4 (Potential D)
5 ms
27
4 (Potential D)
10 ms
28
4 (Potential D)
20 ms
29 – 31
4 (Potential D)
–