![Lütze LION-DI16-DO8-HV Скачать руководство пользователя страница 41](http://html1.mh-extra.com/html/lutze/lion-di16-do8-hv/lion-di16-do8-hv_operating-instructions-manual_1951223041.webp)
LION I/O Modules
▪
Product Description
41
7.5
LED Status
When powering the SIL2 I/O modules, a selftest will be started. All LEDs of the
module will turn on for 500 ms.
Every SIL2 IO module has an L-Bus² status LED (LB) and a module status LED
(MS).
Abb. 37: LED Status LB, MS
Abb. 38: LED – Digital Inputs
LED
Color
Status
Description
LB
MS
green
green
flashing fast
(2 x 5 Hz + break)
on
Adressing of the module
LB
MS
green
green
flashing slow
(2 Hz)
on
Configuration of the module
LB
MS
green
green
on
on
L-Bus
2
is running
LB
MS
green
red
on
flashing slow
(2 Hz)
Limited run
I/Os, peripherals
malfunctioned
LB
MS
red
red
on
on
Fail safe
No communication
LED
Color
Status
Description
I1 – I16
yellow
off
on
flashing fast
(2 x 5 Hz + break)
Input switched off
Input switched on/operating
Error at the input
I10
I9
I12
I11
I14
I13
I16
I15
I2
I1
I4
I3
I6
I5
I8
I7