LION I/O Modules
▪
Product Description
42
Abb. 39: LED – Digital Outputs
7.6
Module Status
During the operation of the system, the modules can be in different status modes:
LED
Color
Status
Description
Q1 – Q8
yellow
off
on
flashing fast
(2 x 5 Hz + break)
Output switched off
Output switched on/operating
Error at the output
Q5
Q6
Q7
Q8
Q1
Q2
Q3
Q4
SIL
relevant
LION-054
During the start and shut down of the system, all outputs are in the safe mode.
SIL
relevant
LION-055
All input signals are “invalid“, which refers to the safe mode.
SIL
relevant
LION-056
If a safety critical error occurs during the start which does not allow a safe
operation the module will be in the safe mode.
Modul Status
Description
local init
After switching on the system, the modules start
the initialisation of the micro controller and the
local module perepherie.
adressing
Wait for the adressing via address bus with
feedback of the communication parameter via
L-Bus
2
.
configuration
The IO module received an address and was
registered at the master. Now it receives
configuration data from the master. The module
acknowledges the receiving and transmits
changed communication parameter because of
the parameterisation if the module has any
configuration data.