Technical data
10
© Lutz-Jesco GmbH 2018
BA-40900-02-V01
Gas warning device
EASYCON GW
Operating instructions
5 Technical data
5.1 EASYCON GW
Information
Value
Voltage supply
100 - 240 V AC, 50 / 60 Hz
Power consumption
max. 20 W
Housing dimensions
302 x 240 x 107 mm
Temperature sensor
-10 ... +100 °C
Load capacity of the relay
230 V AC, 5 A (ohmic resistive load)
Load capacity of the optocoupler
80 V DC, 5 mA
Load capacity of the bugle relay
250 V AC, 10 A (ohmic resistive load)
Analogue outputs
0/4 - 20 mA, max. load 500 ohms
Interfaces
Ethernet Modbus TCP/IP
Protection class
IP 65
Ambient temperature
-5 ... +45 °C
Air humidity
max. 95 %, non condensing
Table 7: Technical data
5.2 Sensors
Information
Value
Measuring gas
Chlorine (Cl
2
)
Chlorine dioxide (ClO
2
)
Ozone (O
3
)
Measuring range
0 - 10 ppm
0 - 1 ppm
0 - 1 ppm
Reaction time
approx. 30 s
Dimensions
135 x Ø 33 mm
Housing material
PVC
Protection class
IP 54
Weight
approx. 0.2 kg
Ambient temperature
-10 ... +40 °C
Air humidity
max. 90 %, non condensing
Service life
max. 2 years, depending on the operating conditions
Table 8: Technical data