background image

Commissioning

Configuration

18

© Lutz-Jesco GmbH 2018

BA-40900-02-V01

Gas warning device 

EASYCON GW

Operating instructions

8 Commissioning

8.1  First steps

You need to make a number of basic settings before operating the device. 
This section leads you through initial commissioning.

Precondition for action:

ü 

The device has been installed in accordance with section 7 
“Installation” on page 12.

ü 

All system parts are ready for operation.

Configuration assistant

With initial commissioning, a configuration wizard will lead you through 
the basic settings: your preferred language; sensors connected; signal 
bugle; and two limit values.

Perform the following steps:

1. 

Set the preferred language and press on the arrow.

2. 

Set up the connected sensors and press the right-hand arrow. Fur-
ther information is available in section 8.2.1.1.

3. 

Set up the bugle and press the right-hand arrow. Further information 
is available in section 8.2.2.1 “Bugle” on page 19.

4. 

Set up the limit values and press the right-hand arrow.

5. 

Press “Yes” in the dialogue field to save the settings.

ü 

The configuration assistant has been ended.

i

You can start the configuration wizard manually by navigating 
Menu item > System > Settings > Configuration and pressing 
on “Edit”.

8.2  Configuration

The device is set up variably and can be individually adapted to meet your 
requirements. As such, it is necessary to adjust the configuration of the 
inputs and outputs to the sensors and signal technology used before 
commissioning.

The following section leads you through the device configuration.

8.2.1  Input side

You can connect up to four sensors for various gases and the tempera-
ture. You can also use eight digital inputs.

8.2.1.1  Sensors

The sensors must be configured individually in the device to enable pre-
cise and error-free measurement of the gases. You can perform various 
settings.

Perform the following steps:

1. 

In the main menu, navigate from System > Inputs to the “Sensors” 
tab.

2. 

In the “Sensors” tab, configure every connected sensor and state the 
following information.

3. 

Measured value: Choose from “Chlorine-gas”; “Chlorine dioxide”; 
“Ozone” or “other”.

4. 

Unit: Choose between “ppm” (parts per million) or “Vol.-%” (volume 
per cent).

5. 

Measuring range: Enter the maximum measuring range of the sensor.

6. 

Limit values: Enter the limit values for the pre-alarm and the master 
alarm.

7. 

Room name: Give the sensor an individual name.

8. 

Slope: State the individual slope of the sensor.

ü 

Configuration of the sensors completed.

8.2.1.2  Temperature

You can connect up to four temperature sensors to the device. This ena-
bles you to measure the temperatures at various positions.

Perform the following steps:

1. 

In the main menu under System > Inputs, navigate to the “Tempera-
ture” tab.

2. 

In the “Temperature” tab, configure every connected temperature 
sensor and state the following information.

3. 

Measuring: Chose between “On” and “Off”.

4. 

Min-alarm: Activate or deactivate the “Min-alarm” and enter a tem-
perature under which the alarm will be triggered.

5. 

Max-alarm: Activate or deactivate the “Max-alarm” and enter a tem-
perature above which the alarm will be triggered.

ü 

Configuration of the temperature sensors completed.

8.2.1.3  Digital

You can use up to 8 digital inputs to evaluate switching statuses and to 
detect them as alarm message which are to be documented in the log-
files.

Perform the following steps:

1. 

In the main menu under System > Inputs, navigate to the “Digital” 
tab.

2. 

In the “Digital” tab, configure the inputs and state the following infor-
mation.

3. 

Type: Select an individual name.

Содержание EASYCON GW

Страница 1: ...Gases Systems Original operating instructions Lutz Jesco GmbH 2018 BA 40900 02 V01 Gas warning device EASYCON GW Operating instructions Read the operating manual The user is responsible for installati...

Страница 2: ......

Страница 3: ...5 Technical data 10 5 1 EASYCON GW 10 5 2 Sensors 10 6 Dimensions 11 6 1 Outside dimensions 11 6 2 Drillhole dimensions 11 7 Installation 12 7 1 Principles 12 7 2 Installation on the wall 12 7 3 Elect...

Страница 4: ...juries WARNING Refers to a potentially hazardous situation Failure to follow this instruction may lead to death or severe injuries CAUTION Refers to a potentially hazardous situation Failure to follow...

Страница 5: ...s through dangerous dosing media n danger to the environment caused by chlorine leaking from the system 2 3 Working in a safety conscious manner Besides the safety instructions specified in this opera...

Страница 6: ...to perform and about the dangers stemming from improper be haviour Trained persons have attended all trainings offered by the operator 2 4 4 Personnel tasks In the table below you can check what qual...

Страница 7: ...ed as non intended use This section is intended to allow you to detect possible misuse in advance and to avoid it Foreseeable misuse is assigned to the individual stages of the product lifetime 3 3 1...

Страница 8: ...ning device n Up to 4 sensors n Operating instructions 4 2 Design and function 4 2 1 Installation example Fig 1 Simple example installation of a chlorine gas room Position Description Position Descrip...

Страница 9: ...rine dioxide or ozone They can also measure the room temperature If the sensors notify too high a value the device will issue an alarm and the connected safety devices such as a signal bugle or sprink...

Страница 10: ...relay 250 V AC 10 A ohmic resistive load Analogue outputs 0 4 20 mA max load 500 ohms Interfaces Ethernet Modbus TCP IP Protection class IP 65 Ambient temperature 5 45 C Air humidity max 95 non conde...

Страница 11: ...changes 180426 BA 40900 02 V01 Gas warning device EASYCON GW Operating instructions 6 Dimensions All dimensions in millimetres mm 6 1 Outside dimensions Fig 4 Outside dimensions 6 2 Drillhole dimensi...

Страница 12: ...the rod 4 You can now open the device 3 Open the device and use the screws for wall mounting Ensure that the device is secured to the wall 4 Close the device again using the rod The device is fitted o...

Страница 13: ...ogue output 4 20 21 36 Digital inputs 1 8 Freely configurable 37 40 Ethernet connection 41 43 Horn relay Clamps 41 42 normal off Clamps 42 43 normal on 44 46 Connection supply voltage Protective earth...

Страница 14: ...5 Open the device housing and lead the cable into the inside of the housing through one of the cable screw connections on the under side of the housing 6 Connect the three coloured wires onto the inp...

Страница 15: ...underside of the device 3 Connect the signal technology used either to clamps 41 and 42 nor mal off or 42 and 43 normal on 4 Note You can adjust the action of the bugle relay in the output set tings...

Страница 16: ...d the device has been switched on Instruction 1 In the main menu navigate to System Outputs Test 4 You will now see all the outputs 2 Select the outputs that you would like to test 3 Press Start 4 The...

Страница 17: ...aximum cable length is 100 m n You must route separately as a bundle the different categories of cables e g power supply data lines and sensitive lines for measuring purposes In this connection cables...

Страница 18: ...eight digital inputs 8 2 1 1 Sensors The sensors must be configured individually in the device to enable pre cise and error free measurement of the gases You can perform various settings Perform the...

Страница 19: ...e exceeding of the limit value the alarm should be activated Configuration of the limit values completed 8 2 2 3 Digital output signals You can control the connected signal technology with digital out...

Страница 20: ...ent of the sensors are accessible here This level is required for device configuration and should only be operated by experienced users n 3 Level The service menu is accessible here This level is main...

Страница 21: ...values which are to be dis played in the trend 3 You can set the scaling of the individual trend display for every value individually Press on the Scaling tab select a sensor and define minimum and m...

Страница 22: ...the new sensor element It contains a short circuit connector which protects the sensor element against ageing during transport and storage 5 Remove the short circuit connector To do so pull on the gol...

Страница 23: ...t the device to its factory settings This deletes the con figuration You must then either load a configuration file or perform the configuration manually Perform the following steps 1 In the main menu...

Страница 24: ...ry is really empty To do so navigate to the menu System Information System values You can view the battery voltage under Battery If the voltage is under 3 V change the battery n Replace the battery Th...

Страница 25: ...mber 123456 will thus be transferred as Address 2000 0x3132 Address 2001 0x3334 Address 2002 0x3536 2003 x Status of the digital inputs Shows the logic of the clamps Not the configured software functi...

Страница 26: ...o type 2021 x Value HIGH WORD Two positions after decimal point 215 2 15 2022 x Value LOW WORD Two positions after decimal point 215 2 15 2024 x Temperature value One position after the decimal point...

Страница 27: ...alue 2 Sensor 1 sensor error Sensor 2 sensor error Sensor 3 sensor error Sensor 4 sensor error Sensor 1 temperature max Sensor 2 temperature max Sensor 3 temperature max Sensor 4 temperature max Senso...

Страница 28: ...mple con los requisitos sanitarios y de seguridad vigentes de las directivas de la U E citadas a continuaci n Esta declaraci n ser invalidad por cambios en el aparato realizados sin nuestro consentimi...

Страница 29: ...anty claim Sender Company Phone Date Address Contact person Manufacturer order no Date of delivery Device type Serial number Nominal capacity nominal pressure Description of fault Service conditions o...

Страница 30: ...the sensor 14 Connecting the signal technology 15 Installation example 8 Installation on the wall 12 Intended purpose 7 Intended use 7 Internal fuse 23 M Maintenance 22 Maintenance intervals 22 N Not...

Страница 31: ...31 Lutz Jesco GmbH 2018 Subject to technical changes 180426 BA 40900 02 V01 Gas warning device EASYCON GW Operating instructions...

Страница 32: ......

Отзывы: