seeTouch
®
guestroom solutions 5
Panel Wiring Instructions
WARNING: Shock Hazard. Turn power OFF to all circuits before installing any part of the
dimming system. Wiring with the power on can result in death or serious personal injury.
NOTICE: Verify that the panel is fed from the correct voltage. A feed miswire or loss of a feed
neutral can cause damage to the equipment.
1.
Pull dedicated feeds
. Each panel requires a 10 A dedicated feed.
2.
Power and control wires must be run in separate conduit or raceways.
Run individual neutrals for input
and each load circuit.
3.
Use 10 A breakers. Do not exceed 2,1 kW per 10 A circuit. (350 W by 6 zones for 2,1 kW max)
4.
Connect load wires to terminals DL1-DL6. Connect all load neutrals for each panel to the neutral
terminals (N).
Load Types
The panel can control incandescent, halogen (tungsten), magnetic low-voltage, and neon/cold cathode load
types. Electronic low-voltage and fluorescent load types can be controlled with an appropriate interface.
• Not all zones need to be connected; however, connected zones must have a load of at least 40 W.
• No zone may be loaded with more than 350 W. Maximum load capacity for each panel is 2,1 kW.
• Panel must not carry more than 8,75 A of total lighting load.
• All Electronic Low-Voltage (ELV) lighting used with the Electronic Low-Voltage Interface must be rated for
reverse phase control dimming
. Before installing an ELV light source, verify with the manufacturer that their
transformer can be dimmed. When dimming, an Electronic Low-Voltage Interface
MUST
be used with the panel.
Wiring Note
Use the bottom right knockouts when pulling PELV wires into the main panel, all other knockouts for
non-PELV use.
1. Strip 25 mm (1 in) of insulation from the PELV cable.
2. Strip 9 mm (3/8 in) of insulation from each wire.
3. Connect the PELV wires to the PELV terminal block. Make sure no bare wire is exposed after making
connections.
4. The recommended installation torque is 0,4 N
•
m (3,5 in-lb) for PELV connections.
(L) 220-240 V
( ) Ground / Earth
Occ Sensors
OCC
SIG
24
V
OCC
COM
L
Load
Load
Load
Load
Load
Load
MUX
MUX
+
24 V
COM
(N) Neutral
Содержание seeTouch guestroom solutions
Страница 2: ...2 seeTouch guestroom solutions...
Страница 16: ...seeTouch MCB PELV 230 V 50 60 Hz 8 75 A 40 350 W 24 V 200 mA...
Страница 17: ...seeTouch 3 seeTouch 24 V Lutron QS 3 4 5 6 7 8 9 10 11 12...
Страница 18: ...4 seeTouch 0 40 C 1 8 6 32 63 8 kg 337 22 286 80 8 235 235 191 25 337 74 86 mm PELV PELV...
Страница 19: ...seeTouch PELV 230 50 60 8 75 A 40 350 24 200...
Страница 20: ...seeTouch 3 seeTouch 24 QS Lutron 3 4 5 6 7 8 Ethernet 9 10 11 12...
Страница 21: ...4 seeTouch 0 40 C 1 8 Lutron 6 32 63 8 337 22 286 80 8 235 235 191 25 337 74 86 PELV PELV...