background image

seeTouch

®

 guestroom solutions   5

Panel Wiring Instructions

WARNING: Shock Hazard. Turn power OFF to all circuits before installing any part of the 

dimming system. Wiring with the power on can result in death or serious personal injury.

   NOTICE: Verify that the panel is fed from the correct voltage. A feed miswire or loss of a feed 

neutral can cause damage to the equipment.

1. 

Pull dedicated feeds

. Each panel requires a 10 A dedicated feed. 

2. 

Power and control wires must be run in separate conduit or raceways.

 Run individual neutrals for input 

and each load circuit.

3. 

Use 10 A breakers. Do not exceed 2,1 kW per 10 A circuit. (350 W by 6 zones for 2,1 kW max)

4. 

Connect load wires to terminals DL1-DL6. Connect all load neutrals for each panel to the neutral 

terminals (N).  

  Load Types

  The panel can control incandescent, halogen (tungsten), magnetic low-voltage, and neon/cold cathode load 

types. Electronic low-voltage and fluorescent load types can be controlled with an appropriate interface.

•  Not all zones need to be connected; however, connected zones must have a load of at least 40 W.

•  No zone may be loaded with more than 350 W. Maximum load capacity for each panel is 2,1 kW.

•  Panel must not carry more than 8,75 A of total lighting load.

•  All Electronic Low-Voltage (ELV) lighting used with the Electronic Low-Voltage Interface must be rated for 

reverse phase control dimming

. Before installing an ELV light source, verify with the manufacturer that their 

transformer can be dimmed. When dimming, an Electronic Low-Voltage Interface 

MUST

 be used with the panel.

  Wiring Note

  Use the bottom right knockouts when pulling PELV wires into the main panel, all other knockouts for  

non-PELV use.

1. Strip 25 mm (1 in) of insulation from the PELV cable.

2. Strip 9 mm (3/8 in) of insulation from each wire.

3. Connect the PELV wires to the PELV terminal block. Make sure no bare wire is exposed after making 

connections.

4. The recommended installation torque is 0,4 N

m (3,5 in-lb) for PELV connections.

 (L) 220-240 V

(   )  Ground / Earth

Occ Sensors

OCC 

SIG

24 

V

OCC 

COM

L

Load

Load

Load

Load

Load

Load

MUX

MUX

+

24 V

COM

 (N) Neutral

Содержание seeTouch guestroom solutions

Страница 1: ...eating and possible damage to other equipment the module must be mounted as shown Failure to provide adequate space for cooling may result in overheating and void the warranty Module hums slightly dur...

Страница 2: ...2 seeTouch guestroom solutions...

Страница 3: ...sing power interfaces Provides individual control of light sources Includes built in astronomic timeclock Includes one contact closure input and 24 V power for occupant sensors or other building manag...

Страница 4: ...and local codes as necessary Mount panel so line mains voltage wiring is at least 1 8 m 6 ft from sound or electronic equipment and wiring Lutron recommends using 6 mm 0 25 in mounting bolts Allow 32...

Страница 5: ...ntrolled with an appropriate interface Not all zones need to be connected however connected zones must have a load of at least 40 W No zone may be loaded with more than 350 W Maximum load capacity for...

Страница 6: ...pply see model descriptions for details 1 2 3 4 1 2 3 4 Panel 1 Non RF Panel with power supply Panels with power supplies can power up to 10 wallstations and cannot have terminal 2 tied to other panel...

Страница 7: ...insulation from both twisted pairs in the wallbox Two 1 0 mm2 18 AWG conductors for common terminal 1 and 24 V terminal 2 These will not fit in terminals Connect as shown One shielded twisted pair 0...

Страница 8: ...on type current probe The current probe should measure no more than 8 75 A 3 Turn loads ON for at least ten minutes If circuit breaker trips turn power OFF then locate and correct miswire or overload...

Страница 9: ...ment and cables not provided Network Connections DIP Switches LED 1 Power LED 2 3 Unused LED 4 RS232 Link Tx LED 5 RS232 Link Rx LED 6 Data Link Tx LED 7 Data Link Rx Data Link to control units proces...

Страница 10: ...CO 4 NC CCO 4 NO CCO 5 NC CCO 5 NO 5 COM CCI 1 CCI 2 CCI 3 CCI 4 CCI 5 COM Contact Closure Outputs Contact Closure Inputs 1 2 3 4 5 6 7 Program button 2 24 V Contact Closure Ratings Five Input Termina...

Страница 11: ...VE IS SPECIFICALLY INCLUDED HEREIN OR IN STANDARD PRINTED MATERIALS PROVIDED BY LUTRON IT DOES NOT FORM A PART OF THE BASIS OF ANY BARGAIN BETWEEN LUTRON AND CUSTOMER AND WILL NOT IN ANY WAY BE ENFORC...

Страница 12: ...1536 Hong Kong 800 901 849 Indonesia 001 803 011 3994 Japan 81 3 5575 8411 Macau 0800 401 Singapore 800 120 4491 Taiwan 00 801 137 737 Thailand 001 800 120 665853 Other countries 65 6220 4666 Contact...

Страница 13: ...obrecalentamietnto y posibles da os a los equipos el m dulo deber montarse como se muestra Si no se dispone del espacio adecuado para el enfriamiento podr a producirse un sobrecalentamiento y quedar a...

Страница 14: ...e potencia Proporciona control individual de las fuentes de iluminaci n Incluye reloj astron mico integrado Incluye una entrada de cierre de contacto y alimentaci n de 24 V para sensores de presencia...

Страница 15: ...acuerdo al peso y a las normas locales seg n sea necesario Instale el cuadro de modo que la alimentaci n del cuadro quede alejada un m nimo de 1 8 m de otros equipos electr nicos o de audio y su cable...

Страница 16: ...seeTouch MCB PELV 230 V 50 60 Hz 8 75 A 40 350 W 24 V 200 mA...

Страница 17: ...seeTouch 3 seeTouch 24 V Lutron QS 3 4 5 6 7 8 9 10 11 12...

Страница 18: ...4 seeTouch 0 40 C 1 8 6 32 63 8 kg 337 22 286 80 8 235 235 191 25 337 74 86 mm PELV PELV...

Страница 19: ...seeTouch PELV 230 50 60 8 75 A 40 350 24 200...

Страница 20: ...seeTouch 3 seeTouch 24 QS Lutron 3 4 5 6 7 8 Ethernet 9 10 11 12...

Страница 21: ...4 seeTouch 0 40 C 1 8 Lutron 6 32 63 8 337 22 286 80 8 235 235 191 25 337 74 86 PELV PELV...

Отзывы: