Appendix: Wiring Load Interfaces
(continued)
Incandescent Load and Control Wiring
Using the FDI-INC-2000
Mounting the Load Interface
The FDI-FTU-16A-120 and the FDI-INC-2000 mount
into a 4 x 4 in. (102 x 102 mm) junction box of a
minimum depth of 3 in. (76 mm). The interfaces can
also be mounted in a 2-gang wallbox with a minimum
depth of 3 in. (76 mm).
Note:
The load interface must only be mounted into a
metal junction box that is properly grounded.
To additional
fixtures
DO NOT WIRE LIVE!
UP
UP
COOPERSBURG, P
A
US
A
Distribution Panel
FDI-INC-2000
Incandescent/magnetic
low-voltage interface
Hot (120 V
)
Green
Black
(120 V
)
White
Red
Orange
Neutral
Hot in
Control
Neutral
Ground
Dimmed hot
output
Fixture ground
Fixture ground
Ground
Neutral
LZC LINK
1
2
3
4
5
6
7
8
9
10
11 12 13 14 15
Lighting Zone Controller
Controlador de zona de luz
Contrôleur de zone d'Éclairage
For installation, refer
to the Lighting Zone
Controller Installer's Guide
(p/n 031-268).
Para la instalación, consulte
la Guía del Instalador de
Controlador de zona de luz
(p/n 031-268).
Pour installation, référer au
guide Contrôleur de zone
d‘Éclairage de l'installateur
(p/n 031-268).
P/N 500-9066 Rev. F
USA, Canada
1-800-523-9466
www.lutron.com
Mexico
Coopersburg, PA 18036 USA
DMW-LZC1
ADDR
+24 V
PS SIG
PS COM
WC COM
WC SIG
+24 V
CIR COM
+15 V
OCC SIG
OCC COM
MUX
MUX
LNK COM
EMERG
SHLD
1-888-235-2910
1
23
4
5
6
7
8
ON
®
100-277 V 50/60 Hz
16 A Max.
LISTED
Energy Management
Equipment 5C81
R
®
Note:
Colors indicated are for
wires coming out of lighting zone
controller.
Caution!
Be sure all the power wires are
completely inside the junction box before
tightening the mounting screws.
R
Installation Guide for Lighting Zone Controllers 29