Installation Guide for Lighting Zone Controllers
This page applies to:
LZC1
Small
Panel
Std.
Panel
Installing Occupant Sensors
OS Common
Signal
+24 V
or +15 V
Maximum of 3
occupant sensors
To OCC COM
To OCC SIGNAL
To 24 V or +15 V terminal
To CIR COM
1
2
3
4
5
6
7
8
9
3: CIR COM
6: +24 V
7: +15 V
8: OCC SIGNAL
9: OCC COM
+24 V
PS Signal
PS Common
Circuit Common
WC Common
WC Signal
+24 V
+15 V
OCC Signal
OCC Common
+24 V
PS Signal
PS Common
Circuit Common
WC Common
WC Signal
+24 V
+15 V
OCC Signal
OCC Common
1 2 3 4 5 6 7 8 9 1
0
1 2 3 4 5 6 7 8 9 1
0
CLASS 2 LOW VOL
T AGE WIRING
+24V
PS Signal
PS Com
Circuit Com
WC Com
WC Signal
+24V
+15V
OCC Signal
OCC Com
MUX
MUX
Link Com
EMERG
Shield
Digital Link
Enlace Digital
Lien Digital
1
2
3
4
5
6
7
8
9
10
11 12 13 14 15
Lighting Zone Controller
Controlador de zona de luz
Contrôleur de zone d'Éclairage
For installation, refer to
the Digital microWATT
Hardware Installer's
Guide (p/n 031-268).
Para la instalación,
consulte la Guía del
Instalador de Digital
microWATT Hardware
(p/n 031-268).
Pour installation, référer au
guide pour quincaillerie
Digital microWATT
(p/n 031-268) de
l'installateur.
P/N 500-9066 Rev. F
USA, Canada
1-800-523-9466
1-610-282-0298 www.lutron.com
Mexico
1
-888-235-2910
1-610-282-1243 www.lutron.com
Coopersburg, PA 18036 USA
DMW-LZC1
R
TEL
FAX
R
LUTRON
LUTRON
+24 V
PS Signal
PS Common
Circuit Common
WC Common
WC Signal
+24 V
+15 V
OCC Signal
OCC Common
1 2 3 4 5 6 7 8 9 10
To occupant sensor
Wire either 15 V
or 24 V
, not
both; check occupant sensor
manufacturer’s specifications
To occupant sensor
Wire either 15 V
or
24 V
, not both;
check occupant sensor
manufacturer’s
specifications
To occupant sensor
LZC1 Connections
Small Panel Connections
Standard Panel Connections
}
Wire to only one
To additional LZCs
(maximum of 2)
Wiring Occupant Sensors
Turn power OFF to the LZC or LZC panel before
connecting occupant sensors.
• LZCs are compatible with standard 15 or 24 V
occupant sensors; follow manufacturers’ instructions
for installation and wire as shown
• Total current drawn for connected occupant sensors
must not exceed 60 mA; use an auxiliary power supply
for loads above 60 mA. Contact Lutron for details.
• Maximum wire length is 250 ft. (76 m)
• Use CIR COM for wiring occupant sensors to more
than one LZC
• Set delay to 0 initially for testing purposes
• Wire size #18 AWG (1.0 mm
2
)
• Follow directions provided with occupant sensors
for mounting and calibration
• Input specification for third-party occupant sensors:
- On state saturation voltage < 2.0 V
or > 10.0 V
- Off-state leakage current < 10 uA
- Open circuit voltage 24 V
maximum
- Short circuit current 4.0 mA maximum
Note:
+24 V signal is made only to
the first LZC if occupant
sensors are wired to multiple
LZCs. Do not c24 V
connections together on
multiple LZCs.
LZC LINK
1
2
3
4
5
6
7
8
9
10
11 12 13 14 15
Lighting Zone Controller
Controlador de zona de luz
Contrôleur de zone d'Éclairage
For installation, refer
to the Lighting Zone
Controller Installer's Guide
(p/n 031-268).
Para la instalación, consulte
la Guía del Instalador de
Controlador de zona de luz
(p/n 031-268).
Pour installation, référer au
guide Contrôleur de zone
d‘Éclairage de l'installateur
(p/n 031-268).
P/N 500-9066 Rev. F
USA, Canada
1-800-523-9466
www.lutron.com
Mexico
Coopersburg, PA 18036 USA
DMW-LZC1
ADDR
+24 V
PS SIG
PS COM
WC COM
WC SIG
+24 V
CIR COM
+15 V
OCC SIG
OCC COM
MUX
MUX
LNK COM
EMERG
SHLD
1-888-235-2910
1
2
3
4
5678
ON
®
100-277 V 50/60 Hz
16 A Max.
LISTED
Energy Management
Equipment 5C81