Installation Guide for Lighting Zone Controllers
This page applies to:
LZC1
Small
Panel
Std.
Panel
Wiring the LZC Link
CLASS 2 LOW VOL
T AGE WIRING
+24V
PS Signal
PS Com
Circuit Com
WC Com
WC Signal
+24V
+15V
OCC Signal
OCC Com
MUX
MUX
Link Com
EMERG
Shield
Integrated Lighting Automation System
®
LISTED
Energy Management
Equipment 5C81
Questions? Call Lutron T echnical Support Center
1-800-523-9466
(24 hrs/7 days)
or visit our web site at www
.lutron.com
POWER INDICA
TOR
On: Caution unit has
power
Off: Unit is not powered or
is not functioning
properly
ADDRESS
SWITCH
Please see installer's
guide for addressing
information.
(p/n 031-198)
STATUS INDICA TOR
Continuous double blink: Unit is
operating properly
Third blink: Unit is communicating
with command center
On or off continuously: Unit is
not operating properly
Daylight
Sensor
W all
Control
Occupant
Sensor
Addressing
P/N 500-9066 Rev
. D
Digital Link
DMW-LZC1 (Lighting Zone Controller)
LUTRON
®
Coopersburg, P
A 18036
100–277 V
~
50/60 Hz
16 A Max.
Digital Link
Enlace Digital
Lien Digital
1
2
3
4
5
6
7
8
9
10
11 12 13 14 15
Lighting Zone Controller
Controlador de zona de luz
Contrôleur de zone d'Éclairage
For installation, refer to
the Digital microWATT
Hardware Installer's
Guide (p/n 031-268).
Para la instalación,
consulte la Guía del
Instalador de Digital
microWATT Hardware
(p/n 031-268).
Pour installation, référer au
guide pour quincaillerie
Digital microWATT
(p/n 031-268) de
l'installateur.
P/N 500-9066 Rev. F
USA, Canada
1-800-523-9466
1-610-282-0298 www.lutron.com
Mexico
1
-888-235-2910
1-610-282-1243 www.lutron.com
Coopersburg, PA 18036 USA
DMW-LZC1
R
TEL
FAX
R
LUTRON
LUTRON
MUX
MUX
Link Com
EMERG
Shield
MUX
MUX
Link Com
EMERG
Shield
Lutron GRX-CBL-46L
series cable
or equivalent
MUX (white)
MUX (purple)
Link common (black)
Emergency (red)
Shield (bare)
#22 AWG (0.64 mm
2
)
#22 AWG (0.64 mm
2
)
#12 AWG (2.5 mm
2
)
#12 AWG (2.5 mm
2
)
#24 AWG (0.5 mm
2
)
LZC link from
Digital
microWATT
router panel,
GRAFIK
7000P
processor, or another
lighting zone controller
To additional LZCs
or LZC panels
(63 LZCs maximum per link)
Pigtail wiring configuration:
Pigtails must be less than 6
inches (150 mm) from wire
connector to terminal block
LZC link
terminals
Danger!
Locate and lock the supply breaker in
the OFF position, or remove the supply fuse
before continuing.
Caution!
Make sure power to all LZCs is OFF
during link wiring.
Notes
• LZC wiring is daisy-chained (from one panel or LZC1
to the next). Pigtails/T-taps must be a maximum
length of 6 inches (150 mm).
• The maximum number of LZCs per link is 63. Panels
contain more than one LZC; take into account the
number of LZCs per panel when calculating LZCs on
each link.
• Wire colors shown assume GRX-CBL-46L is used.
The orange wire is unused.
• The LZC link is considered PELV (Class 2: USA). Do
not run in the same conduit as line voltage.
LZC LINK
1
2
3
4
5
6
7
8
9
10
11 12 13 14 15
Lighting Zone Controller
Controlador de zona de luz
Contrôleur de zone d'Éclairage
For installation, refer
to the Lighting Zone
Controller Installer's Guide
(p/n 031-268).
Para la instalación, consulte
la Guía del Instalador de
Controlador de zona de luz
(p/n 031-268).
Pour installation, référer au
guide Contrôleur de zone
d‘Éclairage de l'installateur
(p/n 031-268).
P/N 500-9066 Rev. F
USA, Canada
1-800-523-9466
www.lutron.com
Mexico
Coopersburg, PA 18036 USA
DMW-LZC1
ADDR
+24 V
PS SIG
PS COM
WC COM
WC SIG
+24 V
CIR COM
+15 V
OCC SIG
OCC COM
MUX
MUX
LNK COM
EMERG
SHLD
1-888-235-2910
1
2
3
4
5
6
7
8
ON
®
100-277 V 50/60 Hz
16 A Max.
LISTED
Energy Management
Equipment 5C81