Installation Guide for Lighting Zone Controllers
This page applies to:
Small
Panel
Wiring
(continued)
Small Panels: Wiring
Connect the input feed wires and the output load wires
to the lighting zone controller as indicated in the wiring
diagrams below. Colors indicated refer to the lighting
zone controller panel terminal block and ballast wire
colors.
From
distribution
panel
Black
Green
Orange
Black
Green
Lutron 3-wire
dimming ballast
Fixture ground
(do not use)
Switched load
Fixture ground
Small Feed-Through Panel
Orange (DH1)
Red (SH1)
Black (H1)
Green/Yellow (G1)
White (N1)
White (N1)
Orange (DH2)
Red (SH2)
Black (H2)
Green/Yellow (G2)
White (N2)
White (N2)
Hot 1
Neutral 1
Hot 2
Neutral 2
Note:
For switchable loads (non-dimming),
make sure address switch 8 on the LZC is in
the ON position.
Input feed and
output line voltage terminals
Black
Green
White
Orange
Black
Green
Lutron 3-wire
dimming ballast
Fixture ground
Switched load
Fixture ground
Orange (DH1)
Red (SH1)
Black (H1)
Green/Yellow (G1)
White (N1)
White (N1)
Orange (DH2)
Red (SH2)
Black (H2)
Green/Yellow (G2)
White (N2)
White (N2)
Output line voltage terminals
Small Panel with Main Lugs
Danger!
Locate and lock the supply breaker in
the OFF position, or remove the supply fuse
before continuing.
Note:
For switchable loads (non-dimming),
make sure address switch 8 on the LZC is in
the ON position.
(do not use)
(do not use)
(do not use)
(do not use)
(do not use)
Note:
Feed wiring is attached to terminal block
at upper right corner of panel.
White
White
White `
Bypass jumper (do not remove at this
time)
Bypass jumper (do not remove at this
time)
Note:
Maximum wire
length from
DMW-LZC1 to
last dimming
ballast is 750
feet (240 m).
Note:
Maximum wire
length from
DMW-LZC1 to
last dimming
ballast is 750
feet (240 m).