Installation Guide for Lighting Zone Controllers
System Overview
LUTRON
LUTRON
LUTRON
LUTRON
LUTRON
LUTRON
One occupant sensor can control a
maximum of 3 LZCs;
One LZC can wire to a maximum of
3 occupant sensors
One LZC link can contain
a maximum of 63 LZCs
One router panel can control a maximum of 3 LZC links
One
GRAFIK
7000P processor panel can control a maximum of 6 LZC links
2
A system
can contain a
maximum of
21
Digital
microWATT
router panels
OR
32
GRAFIK
7000P
processor
panels
1
To
Digital
microWATT
server or
other
GRAFIK
7000P
processor
panels
1
One LZC can wire to a maximum
of 3 wall controls;
One wall control can control a
maximum of 3 LZCs
One LZC can wire to a maximum of
1 daylight sensor;
One daylight sensor can control a
maximum of 1 LZC
Lighting load
System Maximums
Component
Digital microWATT
Router Panel
GRAFIK
7000P Processor Panel
on a
Digital microWATT
system
on a
GRAFIK
7000 System
Processors or router panels per system
21
32
RS485 lighting zone controller (LZC) links per panel
3
6
2
LZCs per system
3969
12096
2
LZCs per router or processor panel
189
378
2
LZCs per RS485 LZC link
63
63
1
GRAFIK
7000 processor panel interprocessor link shown;
GRAFIK
7000P processor panel user interface link not
shown
2
Actual maximum may be less depending on
GRAFIK
7000P processor panel model used
This page applies to:
LZC1
Small
Panel
Std.
Panel
Digital
microWATT
TM
router panel or
GRAFIK
TM
7000P
processor
Typical One-Line Drawing
Small LZC panel
Individual LZC (DMW-LZC1)
Standard LZC panel
(not shown to scale)