CDD34.008-HF to CDD34.032-HF
1)
Data referred to output voltage 400 V and switching frequency 8 kHz
.
Designation
Technical data
CDD
34.
008-
H
F
CDD
34.
010-
H
F
CDD
34.
014-
H
F
CDD
34.
017-
H
F
CDD
34.
024-
H
F
CDD
34.
032-
H
F
Output, motor end
1)
Device rated power
5.4 kVA
6.9 kVA
9.7 kVA
11.8 kVA
16.6 kVA
22.2 kVA
Voltage
3 x 0 ... 400/460 V
Continuous current (RMS) (I
N
)
7.8 A
10 A
14 A
17 A
24 A
32 A
Peak current 1.8 x I
N
for 30 s
14 A
18 A
25 A
31 A
43 A
58 A
Rotating field frequency
0 ... 1600 Hz
Switching frequency of power stage
4,
8
, 12, 16 kHz
Input, mains side
Mains voltage
3 x 400 V / 3 x 460 V -25 % +10 %
Current (with line choke)
8.2 A
10.5 A
14.7 A
17.9 A
25.3 A
33.7 A
Frequency
50/60 Hz ±10 %
Power loss at 4 / 8.16 kHz [W]
150 / 177
187 / 222
225 / 283
270 / 340
330 / 415
415 / 525
Braking chopper power electronics
Peak braking power with int.
braking resistor (only with version
CDD34 ..., Wx.x, BR)
6.0 kW
at 90
Ω
6.0 kW
at 90
Ω
6.0 kW
at 90
Ω
Minimum ohmic resistance of an
externally installed braking resistor
81
Ω
47
Ω
22
Ω