SPC Bridge KNX User Manual
Revision
1.0
Page
20 of 25
Reference
2020-111
For user ids > 255 (e.g the FlexC user) the
value will be 255.
Will be sent to KNX bus when Area mode
changes to Fullset (and if value changes of
other reason e.g at startup)
+15
Area X fail to set
reason
0 = Area fullset succeeded,
1 = Interlocked,
2 = Calendar was preventing area fullset,
100 (0x64) = An area was preventing area
fullset,
101 (0x65) = A (open) zone was preventing
area fullset,
102 (0x66) = An alert was preventing area
fullset,
200 (0xC8) = Other reason was preventing
area fullset
Will be sent to KNX bus every time Area
mode changes to new value and if value
changes of other reason e.g at exit delay and
startup.
DPT 5
1-byte
CR-T-
X = 1 to maximum number of areas (16).
* Datapoint address = 30 + (X-1) * 15 + ‘relative address’.
** Value is based on Alarm status for zone types Alarm, Exit/Entry, Glassbreak and Exit/Entry2.
*** Value is based on Alarm status for zone type Fire.
**** Value is based on Alarm status for zone type Tamper and Tamper status for all zone types.
5.2.6
SPC Zone Status
For
each SPC zone
(input) following Group Objects will be available:
Datapoint
Address
Name
Values
Datapoint Type
Length
Flags
300 + X
Zone X state
0 = Zone is Closed,
1 = Zone is Open
DPT 1
1-bit
CR-T-
560 + X
Zone X status
0 = OK,
1 = Inhibited,
2 = Isolated,
3 = Soak,
4 = Tamper,
5 = Alarm,
6 = OK,
7 = Trouble,
8 = Masked,
9 = Post Alarm
DPT 5
1-byte
CR-T-
X = 1 to maximum number of zones (256).