![Lundix It SPC Bridge KNX Скачать руководство пользователя страница 17](http://html1.mh-extra.com/html/lundix-it/spc-bridge-knx/spc-bridge-knx_user-manual_1950058017.webp)
© PROPERTY OF LUNDIX IT SWEDEN, ALL RIGHTS RESERVED – THIS DOCUMENT AND THE INFORMATION CONTAINED THEREIN ARE CONFIDENTIAL – THE DISCLOSURE OR OTHER COMMUNICATION, COPYING, REPRODUCTION
AND ANY USE WHATSOEVER IS FORBIDDEN WITHOUT THE WRITTEN AUTHORIZATION OF LUNDIX IT.
SPC Bridge KNX User Manual
Revision
1.0
Page
17 of 25
Reference
2020-111
Datapoint Address
Usage
1 to 10
Global system objects
11 to 20
SPC area command objects
21 to 30
SPC zone command objects
31 to 270
SPC area status objects
301 to 556
SPC zone state objects
561 to 816
SPC zone status objects
817 to 1000
Available for future features
The map is designed for an absolute maximum of 16 areas and 256 zones
.
5.2.2
Global System Objects
Following global system global Group Objects will be available:
Datapoint
Address
Name
Values
Datapoint Type
Length
Flags
1
SPC com status
0 = SPC communication is under initialization
(datapoint values are not reliable),
1 = SPC communication is OK,
2 = SPC communication has failed (datapoint
values are not reliable)
To test SPC communication please see section
4.3.
DPT 5
1-byte
CR-T-
10
Scene control
output
Common output for scene numbers sent to the
KNX system when specified events occur. An
individual scene number can be assigned to
following SPC events:
Area X becomes unset
Area X becomes partset A
Area X becomes partset B
Area X becomes fullset
Area X reports an intrusion alarm *
Area X reports a fire alarm **
Area X reports a tamper alarm ***
Area X reports a confirmed alarm
Area X reports all alarms are
restored
(X = 1 to maximum number of areas, e.g. 16)
The scene number is sent each time the
assigned event occurs.
DPT 18
1-byte
C—T-
* Value is based on Alarm status for zone types Alarm, Exit/Entry, Glassbreak and Exit/Entry2.
** Value is based on Alarm status for zone type Fire.
*** Value is based on Alarm status for zone type Tamper and Tamper status for all zone types.
5.2.3
SPC Area Commands
Common for all SPC areas
following Group Objects for commands will be available:
Содержание SPC Bridge KNX