Datapoint
Address
Name
Values
Datapoint Type
Length
Flags
11
Area unset
command
ID of area to unset
The success/error of the command is
reported in “Area command reply status”.
DPT 5
1-byte
C-W--
12
Area partset A
command
ID of area to partset A
The success/error of the command is
reported in “Area command reply status”.
DPT 5
1-byte
C-W--
13
Area partset B
command
ID of area to partset B
The success/error of the command is
reported in “Area command reply status”.
DPT 5
1-byte
C-W--
14
Area fullset
command
ID of area to fullset (immediately)
The success/error of the command is
reported in “Area command reply status”.
The fail to set reason is reported in “Area fail
to set reason”
DPT 5
1-byte
C-W--
15
Area delayed fullset
command
ID of area to fullset when exit time has
expired
The success/error of the command is
reported in “Area command reply status”.
The fail to set reason is reported in “Area fail
to set reason” (after exit time has expired or
been canceled)
DPT 5
1-byte
C-W--
20
Area command
reply status
0 = Last area command succeeded,
1-255 = Area command failed error code.
Codes are listed in section 7.1 SPC Command
Error Codes.
DPT 5
1-byte
CR-T-
Area ID = 1 to maximum number of areas (16).
5.2.4
SPC Zone Commands
Common for all SPC zones
following Group Objects for commands will be available:
Datapoint
Address
Name
Values
Datapoint Type
Length
Attributes
21
Zone inhibit
command
ID of zone to inhibit
The success/error of the command is
reported in “Zone command reply status”.
DPT 5
1-byte
C-W--
22
Zone deinhibit
command
ID of zone to deinhibit
The success/error of the command is
DPT 5
1-byte
C-W--