Lucent Technologies Lineage
®
2000 25A Ferroresonant Rectifier J85502A-1
Issue 4 May 1998
Spare Parts and Replacement Procedures 8 - 19
6. Disconnect P2 header connector from the CM1 option
board, leads 11 and 12.
7. Remove the CBA1 bracket assembly as described in “DC
Circuit Breaker (CBA1) and Bracket.”
8. Remove the CA1 board from its support standoffs as
described in “CA1 Snubber Board.”
9. Remove the thyristor Q1 from its bracket as described in
“Thyristor (Q1).” Then remove the bracket by removing
the two mounting nuts on the side wall.
10. Remove the ac inductor L1 noting “Rear Compartment
Components.”
11. Remove the four nuts and two screws fastening the center
mounting plate to the chassis.
12. Remove the four nuts that hold T1 to the chassis.
13. Carefully slide the center mounting plate forward so that it
lies diagonally across the chassis.
14. Slide T1 to the right and then lift straight up and out of the
chassis using proper lifting equipment of at least
200-pound capacity.
Rectifier Diode
Test and/or
Replacement
If not already done, perform the diode heat sink assembly
procedure.
1. Remove the nut from the stud that secures the diode to the
heat sink. The stud can be anode or cathode of diode, see
the rectifier SD-82604-01 to determine. Lift the diode
body from the heat sink by the “pigtail” side, opposite of
stud side, and save the removed thermal pad for
reinstallation.
2. The diode is now electrically isolated for test purposes.
3. If this procedure is being performed to test a diode, skip to
Step 8. To replace a diode that is known to be defective,
continue with Step 4.