7 - 6 Troubleshooting and Adjustments
Issue 4 May 1998
RFA problem has been cleared. Otherwise, continue
the procedure.
c.
If replacing the CM2 control board does not clear the
problem, then windings 11 and 12 of T1 may be open.
Try the following:
–
Check the wiring to the thyristor (Q1). (See
Figure 5-2.)
–
Check for defective thyristor. Replace, if
defective, following procedure in Section 8.
Calibrate CM3
Digital Meter
Refer to Figures 5-2 and 7-1.
1. Loosen the locking screws and open the door of the
rectifier.
2. Locate the CM3 digital meter board on the inside of the
door.
Note
Calibration is not feasible unless the DMM test meter has an
accuracy of ±0.02 percent or better.
Caution
For Series 1 or 2 CM3 boards, use extreme care when
removing the board from the support standoffs.
Notes
A Series 3 CM3 board can be calibrated without removing
the board from the support standoffs. A Series 1 or 2 CM3
board must be removed from the support standoffs to
calibrate the meter.
A Series 3 CM3 board can be identified by the designation
“AM3” which is stamped on the wiring (noncomponent) side
of the board. A partial sketch of CM3 boards is provided in
Figure 7-1.