Lucent Technologies Lineage
®
2000 25A Ferroresonant Rectifier J85502A-1
6 - 2 Testing
Issue 4 May 1998
Tools and Test
Equipment
The following items are needed for testing the rectifier.
•
DMM (Digital Multimeter) Fluke 8060A or equivalent
meter having 0.02 percent accuracy on dc scale
•
Battery Plant Simulator Test Set, customer constructed, or
equivalent (see Figure 6-1)
•
DC dummy test load, 26-volt (24-volt rectifier) or 52-volt
(48-volt rectifier) with adjustment to provide a load of 30
amperes, 120 percent of the rectifier’s rating
•
Jeweler's screwdriver for adjusting potentiometers
Figure 6-1: Battery Plant Simulator Test Set
+27V
Red Test Clip
To P2A-5 of CM2
To P2A-25 of CM2
To P2A-16 of CM2
To P2A-4 of CM2
To P2A-6 of CM2
To P2A-39 of CM2
To P2A-38 of CM2
To P2A-34 of CM2
To P2A-37 of CM2
To P2A-31 of CM2
To P2A-27 of CM2
To P2A-2 of CM2
Blue Test Clip
See Note
White Test Clip
Black Test Clip
To P2A-12 of CM2
BAT
R2
R1
2150
2150
1 WATT
2150
1 WATT
2150
1 WATT
2150
1 WATT
R3
R4
R5
MAN
1
1
1
1
1
2
2
2
2
2
3
3
3
1
1
1
2
2
2
F1
F2
1 1/3
1 1/3
TR
PWR
HV
RS
RFA
TRH
PH
MAN
RFA
TRH
PH or LOA
DPG
TR48
HV48
RS
RSR
APG
R+
R–
V–
V+
+27V Return
Note:
Use 24 AWG multiconducting wire and 40-pin female connector from Amp, Inc., Harrisburg, PA.
Cable will then plug into
connector on
board. For example, the wire coming from PH,
shown above, must be terminated on pin 12 of the new connector, and RS on pin 34, etc. The
suggested Amp hardware part numbers are:
P2A
CM2
1-102398-8 (housing)
1-102537-8 (cover)
1-102536-8 (cover)
For the remaining 4 extension wires outside the brace, terminate in miniature alligator clips color
coded as shown.