2000 ECS Battery Plant H569-416
3 - 18 Engineering, Planning & Ordering
Issue 2 August 1996
larger wire size requirements. Table 3-D specifies the
equipment, the terminal lug requirements, the maximum wire
size to be terminated directly without H taps, the terminal lug
center spacing, the crimp tool to use, the required fasteners, and
provisioning information.
Terminal lugs and hardware not provided may be ordered from
Table 3-E.
Table 3-D: Field Wiring Specifications
Load Side
Return
Side
Lug Wire
Size
Center
Space
(inches)
Crimp Die Required
Hardware
Lug
Provided
Hardware
Provided
3-50 A
Crkt Brkr
Single
Hole
Double
Hole
12 AWG
10 AWG
8 AWG
6 AWG
5/8
Red
10-32
Screw
Yes
Yes
60-100A
Crkt Brkr
Adapter
Double
Hole
Adapter
Double
Hole
2 AWG
5/8
Blue
10-32 Nut/
Screw
No
Yes
100A Crkt
Brkr
Single
Hole
Double
Hole
2 AWG
5/8
Brown
1/4-20
Screw
No
Yes
225A Crkt
Brkr
Single
Hole
Double
Hole
4/0 AWG
1
Yellow
5/16-18
Screw
No
Yes
-48V Fuse
Panel
Single
Hole
Double
Hole
10 AWG
5/8
R5473
10-32
1/4-20
Nuts
No
Yes
Battery
Leads
Double
Hole
Double
Hole
4/0 AWG
1
Yellow
5/16-18
Nuts
No
Yes
AC to RSA
Single Hole
12 AWG
R5473
10-32
Nuts
Yes
Controller
Alarms
Terminal Block
22 AWG
N/A
N/A
Central
Office
Ground
Double Hole
4/0 AWG
1
5/16 nuts
Yes
Yes