Lucent Technologies -48V CPS4000/CPS4000 PLUS Cabinet Power System
Issue 13 December 2000
Engineering and Ordering 3 - 19
Ordering Information, continued
Output Assembly
Hardware
Table 3-G: Output Assembly Hardware
List
Connector Function
Mating Connection
Lucent Technologies
Commercial
31 - 37
TB1
Battery
positive load
return
847415858 Kit for 6 ga wire
provides (5) T&B 54205UF 45°
lug, (5) T&B 54205 straight lug,
(20) 1/4-20 nut with integral
belville, (8) frame mounting
screws
or
847439841 Kit for 2 ga wire
provides (5) T&B 54208UF 45°
lug, (5) T&B 54208 straight lug,
(20) 1/4-20 nut with integral
belville, (8) frame mounting
screws
Order (1) kit per shelf.
For 6 ga: T&B 54205UF
45° lugs
For 2 ga: T&B 54208UF
45° lugs
TBM5S tool
(2) 1/4-20 nuts with
integral belville per lug
TB2
Battery
negative
For 6 ga: T&B 54205
straight lugs
For 2 ga: T&B 54208
straight lugs
(2) 1/4-20 nuts with
integral belville per lug
TB3
Primary
output bulk
feed
negative
31, 36,
37
J14
Converter
output
847450772 Kit provides (1)
secondary output wire set
equipped with (12) 14 AWG
power conductors and (2) 20
AWG alarm conductors
48" long
Amp 770023-1
15-position
MATE-N-LOK II plug
equipped with Amp
770008-3 sockets
Amp crimping tool
90546-1
31 - 37
J9
Fuse alarm
from
external
distribution
panel
847415841 kit provides 27" fuse
alarm wire set; distribution end
must be terminated and should
provide an isolated contact
closure.
(1) kit optional per shelf.
Wire set equipped with
(1) Amp 350777-7 plug
and (2) Amp 350537-3
sockets. Order Amp tool
90298-2.
31, 35,
36, 37
J10-13
Thermal
probe
847198751 Thermistor kit
provides (1) thermal probe with
5-foot connecting wire included.
Optional kit. 4 kits per plant
maximum.
Not available