Product Description 2 - 27
CPS4000
CPS4000 PLUS
Boost Voltage
N/A
58.1Vdc (using ES660C rectifier)
Efficiency
86% typical
88.5% (using ES660C rectifier)
Output Voltage
Regulation
±
0.5%
±
0.5%
Output Noise:
Wideband Noise
(Ripple)
Electrical Noise
100 millivolts peak to peak
maximum, over the range 10
Hz to 20 MHz
100 millivolts peak to peak
maximum, over the range 10 Hz to
20 MHz
<
32 dBrnc
<
32 dBrnc
Load Share Accuracy
1.25 amperes
1.50 amperes (maximum)
Maximum Discharge
Current
85 amperes per shelf
170 amperes per plant
85 amperes per shelf
170 amperes per plant
Maximum Recharge
Current
Installed rectifier capacity
minus plant load
Installed rectifier capacity minus
plant load
Low-Voltage Disconnect 40.5 ±0.5 volts or 42 ±0.5 volts 40.5 ±0.5 volts or 42 ±0.5 volts
Heat Dissipation
111 watts (380 BTU/hour)
maximum per ES660 rectifier
(Note 3)
106 watts (363 BTU/hour)
maximum per ES660C rectifier
Power Factor
>0.98 for loads >60% of full
load
>0.98 for loads >60% of full load
Note 1: Low-voltage disconnect protection per plant is limited to 150 amperes.
Note 2: Maximum output current capability with ES660C rectifiers only.
Note 3: Input current specified at input voltage of 240 volts, an output of 54.5V and 12.5A,
and efficiency of 86%.
Table 2-F: Rectifier Plant Specifications