9.2 Stepping on unit
Task
Inspection Interval
IEC Fan bearing conditions: Check the replacement interval in the motor
maintenance instructions.
If the motor is equipped with re-greasing nipples, the normal lubrication period is
15,000–30,000 h. The grease amount and type are given in the motor nameplate or
the motor manual.
1 year
Check the correct deflection of the vibration dampers (when needed, replace the
vibration dampers with new ones that Fincoil LU-VE Oy supplies).
1 year
Fasten all the connection terminals correctly.
1 year
You can use the liquid cooler top cover plates as a service desk. Alfa LU-VE recommends installing handrails
and using safety harness. Solutions for handrails and mounting legs are available from Alfa LU-VE.
9.2 Stepping on unit
WARNING:
If you must step on the unit for maintenance purposes, always wear safety shoes.
Use proper safety devices that prevent falling.
Do not step over SM/SRM
™
units.
SM
™
/SRM
™
and SD
™
models
On the left, there is the SM/SRM
™
model. Do not step over the units.
On the right, there is the SD
™
model. Walkable areas are marked in
Figure 42: Walkable areas of AlfaSolar
on page 73.
©
Alfa LU-VE, Rev-04
72
Alfa LU-VE is a trademark registered and owned by LU-VE Group.
Alfa LU-VE reserves the right to change specifications without prior notification.