7.7 Fans and fan connections
Figure 27: Fans with EC motors (P
e
= 700 W) - Electrical connections: Motor junction box
Caution:
Water penetration on the leads or wires. Water enters at the cable end on the customer's
side and may damage the device.
Caution:
The maximum air temperature for an EC fan package is 60 ... 65 °C.
Fan packages with IEC motors
Note:
This option is only for SR
™
models.
The fans are direct driven axial fans. The fan motors are 3-phase squirrel-cage motors built according to the
IEC standards, designed for outdoor use and provided with condensing water outlets, shaft seals and self-
lubricating bearings. The motors are suitable for 400 V/690 V 50/60 Hz electric network. Their protection class,
except for condensing water outlet, is IP54 or IP55 (excluding waterholes) as a standard. The motors are
prewired to the service switches (IP65).
Ask the liquid cooler manufacturer about the technical data of the fan motors.
If the unit stands inactive for a long period, we recommend you to anticondensate the heater installation to the
fan motors.
When using inverter with the fan motors, ensure that you do not exceed the recommended cable lengths and
that the fan motors are sufficiently protected from excessive du/dt and overvoltage spikes.
Note:
Check the product nameplate about motor electrical connections.
©
Alfa LU-VE, Rev-04
52
Alfa LU-VE is a trademark registered and owned by LU-VE Group.
Alfa LU-VE reserves the right to change specifications without prior notification.