pH Control
- 88 -
MTD75 Operation Guide
pH Control
Output Configuration
Depending on the trigger selected the relay output can be configured to operate as an “On/Off”
output, a “Pulse” output or a “Time Proportional” output.
When the output is set to “Pulse” the user can select the “Stroke Rate” which is the frequency of the
output pulses. The output pulse width is fixed at 0.2 seconds.
When the output is set to “Time Proportional” the user can select the “Cycle Time” which is the sum of
the on and the off times. The user can also select the “Proportional Band” over which the proportional
timing is active. For example for a pH setpoint of 10.00pH, a band of 1.00pH and the trigger low was
entered. When the reading falls below 9.00pH the relay would be energised, as the input rises and
approaches the set point the control relay starts to cycle on and off with the on time reducing and the
off time increasing, respectively.
Bleed Inhibiting
The facility has been provided to allow the user to inhibit any Bleed operations during and for a period
after, the pH Control dose. The period of the Bleed Inhibit can be set from 00:00 to 24:00 hours. When
the Bleed Inhibit is set to 00:00, the Bleed operation will be inhibited only for the duration of the pH
Control dose. Only available if the Bleed relay has been enabled.
Pre-Dose Bleeding
The MTD75 provides the user with the option to define a short Bleed operation before initiating the pH
Control Dose, this can be defined from 1 second to 99 minutes. NB. If a bleed inhibit occurs during a
pre-bleed operation the pre-bleed will be terminated and the Biocide dose initiated immediately. Only
available if the Bleed relay has been enabled.
Dose Alarm Timer
To prevent the occurrence of overdosing when using the “pH” trigger, the user can define an “Alarm
Time”. If the dose relay remains active for longer than this set period the system will deactivate the
relay, flash the pH Control LED on the front panel and display the “Dose Alarm” message in the pH
Control section of the main display. To cancel the alarm and re-enable the dose relay the user needs to
press the “ACK” button on the front screen and select pH Control from the list.
Manual Dosing
To provide some flexibility in setting up and adjusting the dosing, the MTD75 is provided with a
“Manual Dosing” option. Selecting the “Manual Dose: Start” option will activate the relay for the time
set in the manual dose duration menu. If the user requires the manual dose to terminate before the
timer runs out select the “Manual Dose: Stop” menu.
Содержание MTD75
Страница 1: ...MTD75 Cooling Tower Controller Operation Guide ...
Страница 2: ......
Страница 5: ...Preface MTD75 Operation Guide 3 Declaration of Conformity ...
Страница 6: ...Preface 4 MTD75 Operation Guide ...
Страница 12: ...Introduction 10 MTD75 Operation Guide Introduction MXD75 Termination Overview ...
Страница 29: ...Installation MTD75 Operation Guide 27 Installation Horizontal Mounting Vertical Mounting ...
Страница 30: ...Installation 28 MTD75 Operation Guide Installation Blank ...
Страница 72: ...Biocide A 70 MTD75 Operation Guide Biocide A BLANK ...
Страница 74: ...Biocide B 72 MTD75 Operation Guide Biocide B BLANK ...
Страница 88: ...Inhibitor 86 MTD75 Operation Guide Inhibitor BLANK ...
Страница 98: ...pH Control 96 MTD75 Operation Guide pH Control BLANK ...
Страница 100: ...Alarm Relay 98 MTD75 Operation Guide Alarm Relay BLANK ...
Страница 108: ...Electrodeless Conductivity Setup 106 MTD75 Operation Guide ECS Setup BLANK ...
Страница 112: ...pH Input Setup 110 MTD75 Operation Guide pH Setup BLANK ...
Страница 118: ...Redox Calibration 116 MTD75 Operation Guide Redox Calibration BLANK ...
Страница 140: ...pH Calibration 138 MTD75 Operation Guide pH Calibration BLANK ...
Страница 142: ...Calibration Reset 140 MTD75 Operation Guide Calibration Reset BLANK ...
Страница 148: ...Current Outputs 146 MTD75 Operation Guide Current Outputs BLANK ...
Страница 152: ...Digital Inputs 150 MTD75 Operation Guide Digital Inputs BLANK ...
Страница 158: ...Configuration 156 MTD75 Operation Guide Configuration BLANK ...
Страница 160: ...Update Software 158 MTD75 Operation Guide Update Software BLANK ...
Страница 164: ...Save Restore Reset 162 MTD75 Operation Guide Save Restore Reset BLANK ...
Страница 166: ...Error Messages 164 MTD75 Operation Guide Error Messages BLANK ...
Страница 172: ...Modbus RS485 170 MTD75 Operation Guide Modbus RS485 BLANK ...
Страница 184: ...Data Logging 182 MTD75 Operation Guide Data Logging BLANK ...
Страница 246: ...Appendix F 244 MTD75 Operation Guide Appendix F Blank ...
Страница 254: ...Appendix G 252 MTD75 Operation Guide Appendix G BLANK ...
Страница 260: ...Notes 258 MTD75 Operation Guide ...
Страница 261: ...Notes MTD75 Operation Guide 259 ...
Страница 265: ......