H100LonWorksManual
31
Inverter Parameters Related to the ‘nciRcvHrtBt’ Variable
Code Number/
Common Area Address
Code Description
Default
Settings
DRV-06
Cmd Source
Fx/Rx-1
Keypad
Fx/Rx-1
Fx/Rx-2
Int 485
FieldBus
Time Event
DRV-07
Freq Ref Src
Keypad-1
Keypad-1
Keypad-2
V1
Reserved
V2
I2
Int 485
FieldBus
Reserved
Pulse
PRT-12
Lost Cmd Mode
None
None
FreeRun
Dec
Hold Input
Hold Output
Lost Preset
PRT-13
Lost Cmd Time
1.0sec
0.1–120.0sec
Caution
When the LonWorks network is used as a command source, the inverter’s lost command time becomes the time set
at ‘nciRcvHrtBt’ and PRT-13Lost Cmd Time added together. However, if the ‘nciRcvHrBt’ variable is set to 0.0 sec, the
lost command protection feature is disabled.