H100LonWorksManual
14
3.2
Basic Field Bus Parameters
3.2.1 Communication Module Information– Option Type (CNF-30)
CNF-30
Option Type
This parameter automatically displays the name of the currently installed communication module.
If the LonWorks communication module is installed, CNF-30 Option Type displays ‘LonWorks.’
If the CNF-30 Option Type does not display any communication module names, this may mean that there is a faulty
connection between the inverter and the LonWorks communication module.
3.2.2 Command Source Options–Cmd Source (DRV-06)
DRV-06
Cmd Source
This parameter is used to select a command source.
To operate the inverter using the Lon Works communication, setDRV-06Cmd Source to ‘4.Fieldbus.’
3.2.3 Source of Frequency Reference Options– Freq Ref Src (DRV-07)
DRV-07
Freq Ref Src
This parameter is used to select a frequency reference.
To provide a frequency reference using the LonWorks communication, set DRV-07 Freq Ref Src to ‘7.Fieldbus.’
3.2.4 Secondary Command Source Options (for switching between two different command sources)
BAS-04
Cmd 2nd Src
BAS-05
Freq 2nd Src
IN-65–71
P1–P7 Define
This parameter is used to provide a second command source (frequency reference and run command) using the multi-
purpose input terminals. If the inverter is operated by remote network commands from network modules such as the
Lon Works communication module, this parameter may be used to stop remote operation and switch to local
operation using the inverter keypad.
This feature requires that the multi-purpose terminals P1–P7 (parameters IN65–71) are set to ‘2nd Source.’
3.2.5 Version information for the installed Communication Module– Fbus S/W Ver (COM-06)