2.7
Maximum Ranges for Different Network Cables
As shown in the following table, the maximum ranges of a network are limited based on the topology and the type of
cables used. Reliable network communication cannot be guaranteed beyond the maximum ranges listed in the table.
BUS Topology
Free Topology
Cable Type
Maximum Bus Length
Belden 85102
2,700 m
Belden 8471
2,700 m
Level IV, 22AWG
1,400 m
JY(St) Y 2x2x0.8
900 m
TIA Category 5
900 m
Cable Type
Maximum Distance between
Devices
Maximum
Total Range
Belden 85102
500 m
500 m
Belden 8471
400 m
500 m
Level IV, 22AWG
400 m
500 m
JY(St) Y 2x2x0.8
320 m
520 m
TIA Category 5
250 m