H100LonWorksManual
16
3.2.8 Display Node Status– Opt Parameter4(COM-13)
COM-13
Opt Parameter4
This read-only parameter is used to display the network interface status. When the interface is operating normally,
‘Configured on-line’ is displayed. This means that the relevant node has been commissioned by the network and is on-
line. ‘Soft’, ‘Bypass’, or ‘Hard off-line’ states indicate that the node failed to participate in the network.
Values
Description
0
Unknown state
1
Not configured
2
Application unassigned
3
Configured on-line
4
Configured off-line
5
Soft off-line
6
Configured bypass off-line
7
Hard off-line, Bypass off-line
3.2.9 Enable Service Pin– Opt Parameter5 (COM-14)
COM-14
Opt Parameter5
This parameter is used to enable the service pin feature without using the service pin switch on the LonWorks
communication module. Set COM-14 Service Pin Enable to ‘1’ to enable the service pin feature. This allows the Lon
Works communication module to send its Neuron ID and Program ID to the network.
Note
The Service Pin may be enabled on the keypad ONCE OLNY, after the inverter has been turned on the first time.
Once decommissioned from the configuration tool, the inverter cannot be commissioned again on a network using
the ‘Enable Service Pin’ parameter. You must turn on the service pin switch on the LonWorks communication module
to connect to the network.