H100LonWorksManual
19
3.2.14 Lost Command Decision Time– Lost Cmd Time (PRT-13)
DRV-06
Cmd Source
DRV-07
Freq Ref Src
PRT-12
Lost Cmd Mode
PRT-13
Lost Cmd Time
This parameter is used to set the time the inverter takes to decide that the command is lost. When the remote
command via network is lost for the lost command decision time (PRT-13 Lost Cmd Time + the time set at
nciRdvHrtBt), the inverter decides that the command is lost.
This feature is available only when DRV-06 is set to ‘4.Fieldbus,’ or when DRV-07 is set to ‘7.Fieldbus.’ If the network
command is recovered before the lost command decision time (PRT-13 Lost Cmd Time + the time set at nciRdvHrtBt)
is passed, the inverter does not output a fault trip and continues normal operation.
Caution
Lost command time protection operates only when the ‘nciRcvHrtBt’ variable is set to any value other than ‘0.’
Lost Command Period
Lost Command Period
Comm Line Status
Command was
recovered before
the Lost Cmd Time.
Lost command was
not detected.
Lost Command was detected.
The inverter runs according to
the Lost Cmd Mode Settings.
Time