Thank you for purchasing 

L

ON

W

ORKS

 Option Board. 

 

SAFETY PRECAUTIONS 

 

 

Always follow safety instructions to prevent accidents and potential hazards from occurring.

 

 

 

Safety precautions are 

classified into “WARNING” and “CAUTION” and their meanings are as

 

follows:

 

 

WARNING 

CAUTION 

 

 

 

The indicated illustrations on the product and in the manual have the following meanings.

 

 

Danger may be present. Read the message and follow the instructions carefully. 

 

                         

Particular attention should be paid because danger of an electric shock may be present. 

 

  Keep operating instructions handy for quick reference. 

 

Read the operating instructions carefully to fully understand the functions of the H100 series and to use it properly

 

  CAUTION 

 

 

Be cautious, when handling the CMOS components of the Option Board.

 

Static may lead to malfunctioning of the product. 

 

Turn off the inverter power, when changing the communication cable. 

Otherwise, you may damage the board or a communication error may occur. 

 

Make sure to insert the Option Board connector to the inverter precisely. 

Otherwise, you may damage the board or a communication error may occur. 

 

Check the parameter unit before setting up the parameter. 

Otherwise, a communication error may occur. 

 

 

 

Improper operation may result in serious personal injury or death.

 

 

Improper operation may result in slight to medium personal   

injury or property damage.

 

 

Содержание CLON-H100

Страница 1: ...ck reference Read the operating instructions carefully to fully understand the functions of the H100 series and to use it properly CAUTION Be cautious when handling the CMOS components of the Option B...

Страница 2: ...the initial installation of the devices This is done by configuring the input and output variables with an installation tool When configuring the input and output variables of the devices the network...

Страница 3: ...r Maximum Number of Nodes Maximum 248 nodes 48bit addressing 64 channels per segment including the Master MaximumTransfer Distance per Segment FreeTopology 500m BusTopology 2700m Available PDO Physica...

Страница 4: ...onWorksManual 4 2 2 Device Layout Connector to the Inverter Connector to Inverter DIP Switch Terminal resistance Service Pin Configuration Communication Connector A B S LED CPU Operation Error Service...

Страница 5: ...alling or removing the communication module while the power is on may damage the inverter or the LonWorks communication module Make sure that the inverter is fully discharged before installing or remo...

Страница 6: ...H100LonWorksManual 6 Install the H100 LonWorks communication module 4 into the connector on the I O board Secure the communication module with the 2 screws supplied with the device 4...

Страница 7: ...H100LonWorksManual 7 Replace the top cover 5 then the keypad 6 Replace the power terminal block cover 7 The inverter is now ready for use 7 5 6...

Страница 8: ...s communication module to a network 2 5 Configuring a Network Warning Turn off the power to the inverter before installation and network connection Installing or removing the communication module whil...

Страница 9: ...inals A and B The following table describes the type and feature of the termination resistance for each switch position Termination Switch Configuration for the H100 LonWorks communication module Swit...

Страница 10: ...communication module download the external interface file H100_LONWORKS XIF from the LSIS web site http www lsis com support download 8 Turn on the power to the inverter and use the keypad to ensure t...

Страница 11: ...on cannot be guaranteed beyond the maximum ranges listed in the table BUSTopology FreeTopology CableType Maximum Bus Length Belden 85102 2 700 m Belden 8471 2 700 m Level IV 22AWG 1 400 m JY St Y 2x2x...

Страница 12: ...Rx 1 0 Keypad 1 Fx Rx 1 2 Fx Rx 2 3 Int 485 4 FieldBus 5 Time Event DRV 07 Freq Ref Src 0 Keypad 1 0 Keypad 1 1 Keypad 2 2 V1 4 V2 5 I2 6 Int 485 7 Fieldbus 9 Pulse BAS 04 Cmd 2nd Src 1 Fx Rx 1 0 Keyp...

Страница 13: ...M 36 Para Status 6 0x0000 0 0xFFFF COM 37 Para Status 7 0x0000 0 0xFFFF COM 38 Para Status 8 0x0000 0 0xFFFF COM 51 Para Control 1 0x0005 0 0xFFFF COM 52 Para Control 2 0x0006 0 0xFFFF COM 53 Para Con...

Страница 14: ...ency Reference Options Freq Ref Src DRV 07 DRV 07 Freq Ref Src This parameter is used to select a frequency reference To provide a frequency reference using the LonWorks communication set DRV 07 Freq...

Страница 15: ...CPU LED An example of COM 09 LED State 1101 LED COM GREEN SERVICE GREEN ERR RED CPU GREEN Status ON ON OFF ON Keypad Display 3 2 7 Display the Neuron ID Opt Parameter1 3 COM 10 12 COM 10 Opt Parameter...

Страница 16: ...pass off line 7 Hard off line Bypass off line 3 2 9 Enable Service Pin Opt Parameter5 COM 14 COM 14 Opt Parameter5 This parameter is used to enable the service pin feature without using the service pi...

Страница 17: ...94 After making changes to the parameters related to configuring Drive Objects using the keypad a communication update is required to apply the changes Set COM 94 Comm Update to Yes to perform a comm...

Страница 18: ...With this feature enabled the selected operation mode is used when the network command is lost Settings Description 0 None Keeps the inverter operation at lost command 1 Free Run The inverter blocks o...

Страница 19: ...re is available only when DRV 06 is set to 4 Fieldbus or when DRV 07 is set to 7 Fieldbus If the network command is recovered before the lost command decision time PRT 13 Lost Cmd Time the time set at...

Страница 20: ...ables Function Variable Name SNVTType Min Max Node Object Status nvoStatus SNVT_obj_status 4 1 2 nvoStatus Variable The following table shows the Node Object states indicated by the nvoStatus output v...

Страница 21: ...rvVolt SNVT_volt nv5 nvoDrvPwr SNVT_power_kilo nv6 nvoDrvRunHours SNVT_time_hour nv7 nc17 nciLocation Optional nc50 nciMaxSpeed Mandatory nc53 nciMinSpeed Mandatory nc48 nciRcvHrtBt Optional nc49 nciS...

Страница 22: ...e is set to a positive number and in the reverse direction Rx when it is set to a negative number Frequency reference information is given by a combination of the nviDrvSpeedScale and nviDrvSpeedStpt...

Страница 23: ...on COMM group set DRV 06 Cmd Source to FieldBus and DRV 07 Freq Ref Src to FieldBus using the keypad These settings configure the inverter to receive run commands and frequency references from the Lon...

Страница 24: ...30 Actual Motor Current nvoDrvCurnt SNVT_amp 0 0 A 3276 7 A Drive Output Voltage nvoDrvVolt SNVT_volt 0 0 V 3276 7 V Actual Drive Power nvoDrvPwr SNVT_power_kilo 0 0 kW 6553 5 kW Drive total running h...

Страница 25: ...n Network output SNVT_amp nvoDrvCurnt Description The nvoDrvCurnt variable is used to output the inverter s output current in amperes A Typical Range 0 0 3276 6 A 0 1 A Inverter Parameters Related to...

Страница 26: ...ange 0 0 6553 4 kW 0 1 kW Inverter Parameters Related to the nvoDrvPwr Variable Code Number Common Area Address Code Description MAK 01 0x0301 Inverter Capacity 4 2 7 nvoDrvRunHours Variable Definitio...

Страница 27: ...nal SCPTMinOutTime Nominal Motor Speed in RPM nciNmlSpeed Mandatory SCPTnomRPM Nominal Motor Frequency nciNmlFreq Mandatory SCPTnomFreq Minimum Ramp UpTime nciRampUpTm Mandatory SCPTrampUPTm Minimum R...

Страница 28: ...cannot be made to the nciMaxSpeed variable while the inverter is running Stop the inverter operation before making changes to the nciMaxSpeed variable The default value for the nciMaxSpeed variable is...

Страница 29: ...e making any changes to the nciMinSpeed variable The default value for the nciMinSpeed variable expressed as percentage is calculated based on the base frequency and the start frequency DRV 19 Start F...

Страница 30: ...dStpt and nviDrvSpdScale variables are not updated for the set time nciRcvHrBt time value PRT 13 Lost Cmd Time the inverter decides that the command is lost It then runs in the operation mode set by t...

Страница 31: ...pad 1 Keypad 2 V1 Reserved V2 I2 Int 485 FieldBus Reserved Pulse PRT 12 Lost Cmd Mode None None FreeRun Dec Hold Input Hold Output Lost Preset PRT 13 Lost CmdTime 1 0sec 0 1 120 0sec Caution When the...

Страница 32: ...he minimum wait time before the output variables nvoDrvSpeed nvoDrvCurnt nvoDrvVolt nvoDrvPwr and nvoDrvRunHours are sent to the network Rather than reflecting the changes in the variables each time t...

Страница 33: ...eq value to 1700 RPM changes the nciNmlFreq value to 56 7 Hz a rounded up value of the DRV 18 Base Frequency value and DRV 18 Base Frequency to 56 66 Hz When the values set at nciNmlSpeed or nciNmlFre...

Страница 34: ...is the default acceleration time that is set as DRV 03 Acc Time Valid Range 0 0 600 0 sec 0 1 sec increments Default 20 0 sec Inverter Parameters Related to the nciRampUpTm Variable Code Number Common...

Страница 35: ...V 04 Dec Time using the inverter keypad either turn off the inverter and then turn it back on or set COM 94CommUpDate to Yes to reflect the changes in the configuration property variables nciNmlFreq n...

Страница 36: ...be used in the formula for the base frequency values The maximum frequency MaxFreq value cannot be set higher than 163 830 of the base frequency Base Freq Therefore the maximum value of the nciMaxSpe...

Страница 37: ...e6 SNVT_count nv14 nvoUsrParaState7 SNVT_count nv15 nvoUsrParaState8 SNVT_count nv16 nviUsrParaCtrl1 SNVT_count nv1 nviUsrParaCtrl2 SNVT_count nv2 nviUsrParaCtrl3 SNVT_count nv3 nviUsrParaCtrl4 SNVT_c...

Страница 38: ...g LS inverters Because these variables are user definable to match with the inverter parameters that the users intend to adjust rather than permanently assigned to certain parameters more convenient a...

Страница 39: ...ontrol 8 0x0000 0 0xFFFF Note When the inverter is used on a Lon Works network COM 50 User Parameter Control Number is automatically set to 8 If the user sets COM 50 to any other value from the keypad...

Страница 40: ...r the output frequency with nvoUsrParaState1 the output voltage with nvoUsrParaState2 and the jog frequency with nvoUsrParaState3 If the inverter is operating at 30 Hz with the DC link voltage of 150...

Страница 41: ...ime nciRcvUsrHrBt time value PRT 13 Lost Cmd Time the inverter decides that the command is lost and runs in the operation mode set at PRT 12 Lost Cmd Mode Lost command time protection operates only wh...

Страница 42: ...and PRT 13 Lost Cmd Time added together However if the nciRcvHrBt variable is set to 0 0 sec the lost command protection feature is disabled 4 3 4 Send Heart BeatTime for User Object Mandatory Defini...

Страница 43: ...t variables nvoUsrParaState1 nvoUsrParaState8 are sent to the network Rather than reflecting the changes in the variables each time they are made a network update is performed when a set period of nci...

Страница 44: ...icates that the H100 LonWorks communication module has not been configured Flashing intermittently indicates that electronic interference is affecting the LonWorks network Inspect network cables to en...