33
In-Band Alarm relay
Alarm tripped
Alarm reset
Alarm = In.Bnd
Hi = 69
Lo = 35
HI Set.Pt Value
The alarm relay will activate when the measured value is below the HI value and above the LO value
in.b
hi
lo
Mode HI Setpoint value LO Setpoint value
LO Set.Pt Value
Out-Band Alarm relay
Alarm tripped
Alarm reset
Alarm = In.Bnd
Hi = 69
Lo = 35
HI Set.Pt Value
The alarm relay will activate when the measured value is above the HI value or below the LO value
OUT.b
hi
lo
Mode HI Setpoint value LO Setpoint value
LO Set.Pt Value