Your analogue output can cover 0-100% of its range over a display range which you can set.
For example, you might want 4-20mA output, for a display range of 500 to 1000.
You would press the Analogue O/P button for 3 seconds, and select 4-20mA
Then set 0% = 500
Then set 100% = 1000
Press the OUTPUT button for 3 seconds. If an output board is fitted, the display will confirm this
and confirm the range chosen by the jumpers on the previous page.
The 0% LED will flash. Select the Output range you want.
Use the
DIGIT
, and buttons to set the display value at which you want 0% analogue
output.
Press
OK
when done.
The 100% LED will flash.
Use the
DIGIT
, and buttons to set the display value at which you want 100% analogue
output.
Press
OK
when done.
When you have finished setting the meter, put the lockout switch in its ON position now, to prevent
your settings from being changed.
DIGIT
OK
ALARMS
AL1
AL2
AL3
AL4
OUTPUT
0% 100%
Analogue Output - page 2
Lockout notes:
Cal Lock switch = OFF when changing. Switch Cal Lock to ON after changing