20
Theoretical cal., no linearisation - page 3
Press the
Set1
button for around 3 seconds
.
theor
will appear briefly, to confirm that you
are in the theoretical calibration mode.
The numeric value will need to be the low
input signal value ...
Next,
In Lo
will appear briefly. Set to the
low input value, which was 4mA according
to the sensor calibration sheet in our
example.
You can change the value of the brightest
digit with the UP or DOWN buttons.
Brighten other digits with the DIGIT button.
Press OK when done...
rd LO
will now appear briefly, followed by a
numeric value, which you can set...
The numeric value will need to be the low
reading value ...
Set to the low reading value, which was
0kg according to the sensor calibration
sheet in our example.
You can change the value of the brightest
digit with the UP or DOWN buttons.
Brighten other digits with the DIGIT button.
Press OK when done...
This completes the Theoretical calibration routine. Please remember to switch the Calibration
Lockout switch ON
Continued from previous pages. ZERO setting ...
theo
04.00
rd.lo
0000