EPCS Configuration Setpoints
WARNING: These setting can affect the functionality of the EPCS and should only be modified if
you are absolutely certain how these changes will impact your refrigeration system.
Zone Trip Pressure
When the zone pressure exceeds either the
Zone Trip Pressure
or the fixed setpoint, the zone
is tripped and the crossover valve is opened.
Select Zone Type
Each EPCS zone must be configured to its vessel's pressure rating. Select 250 PSIG Rated
Vessel or, if you are certain the vessel is rated for 300 PSIG, select 300 PSIG Rated
Vessel. Under no circumstance should a value be selected which is higher than the vessel's
rating.