between the buyer and Logix that this is the buyer’s responsibility. It is the responsibility of the installer to ensure that the
installation is in compliance with all national and local codes. Installation should only be attempted by a licensed electrician
familiar with codes, standards, and proper safety procedures for line-voltage installations.

 Caution

Read this Entire Document Prior to Installation and Operation of this Unit.

 Warning

Risk of Electrical Shock. Severe injury or death can result from electric shock during contact with line voltage wiring and
equipment. Disconnect and lock-out all power sources during installation and service.

M

OUNTING

L

OCATION

C

ONSIDERATIONS

1. Overall Dimensions - 13.4"W x 13.0"H x 7.1"D
2. Environmental

a. Temperature

i.

Operating Temperature -22°F - +122°F (-30°C - +50°C)

ii.

Protect from direct sunlight which can cause the enclosure to exceed its operating temperature limit.

b. Humidity

i.

Maintain operating and storage relative humidity between 10% and 95%, non-condensing.

c. Mechanical Considerations

i.

The UL-Rated Type 4X enclosure allows mounting in indoor or outdoor locations.

ii.

Mount in a low vibration location.

iii.

Mount in a location providing protection from damage.

iv.

Mount in a location providing easy access for servicing.

v.

Mount in proximity to controlled or monitored equipment to reduce installation costs.

3. Networking Considerations

a. WiFi signal range is diminished by walls, metal objects, etc.
b. Ethernet (CAT5e) network cabling is limited to 328 feet.  Longer distances require additional equipment (not

provided) such as a repeater or fiber-optic link.

c. Modbus RTU twisted pair cabling is limited to 4000 feet total.

P

OWER

R

EQUIREMENTS

1. The Agility Controller requires 100VAC – 125VAC, 50/60Hz power and consumes up to a total of 10 Amps (including

controller and controlled devices).  The controller itself requires 0.5 Amps leaving 9.5 Amps available for controlled
devices.

2. Do not “tap in” to the Agility Controller to power other equipment or otherwise alter the intended function of the

Agility Controller.

S

ECURITY

C

ONSIDERATIONS

1. Network Security Considerations - Agility is not designed to be connected directly to the public Internet.  Rather it

should reside behind a firewall on a private network.  Remote access, if any, should be implemented through a secure
VPN connection.

2. The Agility Controller’s WiFi network name and password are field configurable.  At a minimum, the WiFi Access Point

password should be changed.

Содержание AGILITY Series

Страница 1: ...e tablet laptop or PC b Built in online help system and documentation 2 Agility Controller Platform a Up to 4 Analog Sensor Inputs for measuring Temperature Pressure Humidity etc b Up to 2 fully isola...

Страница 2: ...variety of applications i Up to 6 fans or pumps in any combination ii 1 alarm output for annunciators or alerting systems iii 1 fan fault alarm input b Fans can be a single speed or Variable Speed wit...

Страница 3: ...bration location iii Mount in a location providing protection from damage iv Mount in a location providing easy access for servicing v Mount in proximity to controlled or monitored equipment to reduce...

Страница 4: ...r equal Limit total network cabling length to 4000 feet QUICK START OVERVIEW 1 Install the Agility Controller following the provided installation instructions and wiring diagrams At a minimum wire the...

Страница 5: ...require additional IT support to determine the Agility Controller s IP address obtained from the existing WiFi Access Point 3 Disable WiFi Access The WiFi interface is disabled WIFI NETWORK SETTINGS P...

Страница 6: ...sk optional Enter the Broadcast Mask for this device If unknown or not required enter 0 0 0 0 d Eth0 Gateway Enter the Gateway address for this device For example 10 0 100 1 The default Gateway addres...

Страница 7: ...c Type Speed i Up to 150Mbps data rate ii IEEE 802 11n g b is compatible with a wide range of WiFi devices 4 Ethernet Network a 10 100 BaseT b TCP IP Protocol...

Страница 8: ...you wish to manually adjust the time and or date Daylight Saving Time Beginning Date Daylight Saving Time Ending Date Starting in March of 2007 daylight time in the United States began on the second S...

Страница 9: ...onnect to Existing join existing WiFi network or Disable WiFi Access Access Point Channel Enter the WiFi Access Point channel This is only utilized for Local Access Point WiFi networks Typical values...

Страница 10: ...uration have your IT department configure this device The Default button forces the network configuration back to the factory configured settings The Agility Controller s MAC Address is shown at the b...

Страница 11: ...not entered the page s settings will still be displayed allowing observation but not modification Setup Passwords To access the Setup Passwords page from the Secure Access menu select Setup Passwords...

Страница 12: ...tripped on a high pressure condition The Functional output will de energize on loss of control power EPCS malfunction pressure sensor fault or pressure sensor wiring fault EPCS Emergency Stop Digital...

Страница 13: ...When the zone pressure exceeds either the Zone Trip Pressure or the fixed setpoint the zone is tripped and the crossover valve is opened Select Zone Type Each EPCS zone must be configured to its vess...

Страница 14: ...nimum all circuits both inside the panel and interfaced to the panel be thoroughly verified as disconnected and safe with a high quality electrical meter which is tested to be functional before and af...

Страница 15: ...ller has sent a message The RX LED indicates the Agility Controller has received a message The Ethernet jack has a green LED which indicates a basic connection to the network It does not indicate that...

Страница 16: ...O Status to ascertain which sensor is faulting Moisture penetration into a sensor s enclosure is the most common source of sensor failure Refer to the sensor installation wiring diagrams for installa...

Страница 17: ...hole at the lowest point to limit moisture related problems 3 Sensor is damaged or faulty and needs replacing Analog Sensor Calibration The Sensor Calibration routine permits small adjustments to fine...

Страница 18: ...ooting The Agility Controller s two analog outputs generate an active 4 20mA signal to control variable speed or position devices including modulating valves and variable speed motors Since the Agilit...

Страница 19: ...ure output voltage with a load connected 1 Connected load is very small less than 25mA and leakage current is causing the output to stay at or near 120VAC 2 Connect a larger load and re measure output...

Страница 20: ...is corrupting the Ethernet network For example a newly installed web camera was improperly configured with the same IP address as the Agility Controller resulting in an address conflict The symptoms...

Страница 21: ...V CR 2032 CH1 CH2 24VAC Power COM 2 COM 1 V Com Data Data Com Data Data Sig1 Ret1 Sig2 Ret2 Analog Outputs Pwr1 Sig1 Com1 Pwr2 Sig2 Com2 Pwr3 Sig3 Com3 Pwr4 Sig4 Com4 Analog Sensor Inputs 3V Battery D...

Страница 22: ...1 C H2 CH1 CH2 CH3 CH4 Analog Configuration Agility Controller VDC 24 0 VDC 1 7 VDC 1 7 24V Power 4 20mA Signal Shi eld Sensor Transmitter Sensor Probe Should be between 23 and 25 VDC About 0 6 VDC 4...

Страница 23: ...ission of The Controls Group In c LOGIX is a registered trademark of The Controls Group Inc Drawing Filename Date Rev Drawn by Title 07 11 2016 Agility Digital Input Output Schematic 01 MAG AgilityDig...

Страница 24: ...3V CR2032 CH1 CH2 ON 24VAC Power COM 2 COM 1 V Com Data Data Com Data Data Sig1 Ret1 Sig2 Ret2 Analog Outputs Pwr1 Sig1 Com1 Pwr2 Sig2 Com2 Pwr3 Sig3 Com3 Pwr4 Sig4 Com4 Analog Sensor Inputs 3V Batte...

Страница 25: ...K Black Or Orange field wiring panel wiring panel terminal block LEGEND R panel screw terminal L2 L2 W 14 L2 L2 P1 P1 NEUTRAL 14 Agility E P C S Wiring Diagram Agility_EPCS_Wiring_Diagram Zone 1 Press...

Отзывы: