3N1
INSTALLATION
Power Cable
Cable A5006221
1. Connect the wire ends of the power cable to 24VDC of
the Savio power connection block:
– blue = negative (–) = terminal 500
– brown = positive (+) = terminal 503
2. Route the cable to the backside of the SCU and plug in
the SCU
Power
connector.
Lamp Tree
Connect the lamp tree cable to the SCU
Lamp tree R(ight)
connector.
Connection (R)
Wire
aux
no connection
blue lamp
green
orange lamp
brown
red lamp
white
common
yellow
LAN Bus to SE
Parts: 1 x cable A5005113.
Plug one cable in the SCU
SE Bus
connector and route the
cable in the left cable channel to the first SE Board.
KA5/KA7 give to the SCU the run/stop state of each machine
side.
Machine Signals
Cable A500750.
1. Plug the connector labeled “right” in the SCU
Machine signals R(ight)
connector.
2. Plug the connector labeled “left” in the
Machine signals L(eft)
connector.
3. Route the cables to the Savio control box.
4. Plug “X15” in the Savio X15 connector.
5. Connect the remaining wires to the KA5 and KA7 relay
contacts.
6. Close the SCU connections cover.
Wire
Relay / contact
Terminal
Side
white
KA5 / COM
562
Right (DX)
brown
KA5 / NO
563
green
KA7 / COM
564
Left (SX)
yellow
KA7 / NO
565
KA5 / KA7
X15