Impinger X2 –Operator Manual
20
Electrical Supply (U.S. and Canada)
(UNITS WITH ANALOG CONTROL BOARD)
Lincoln X-2 ovens DO NOT utilize a control power transformer to supply the 120 volts required for controlling the
oven. Regardless of electrical configuration (single or three phase) a neutral wire is required to provide 120 volt
control power. All wiring must conform to local building codes.
Single Phase (Standard)
Lincoln X-2 ovens that are configured to operate on single-phase power will require a 20 amp single phase,
120 / 230VAC, three wire with ground, 60 Hz service: Two (2) “hot” or current carrying leads (red and black),
one (1) neutral (white) and one (1) equipment ground (green).
Three Phase (Optional)
Lincoln X-2 ovens that are configured to operate on three-phase power will require a 20 amp three phase,
120 / 230 VAC, four wire with ground, 60 Hz service: Three (3) “hot” or current carrying leads (red, blue &
black), one (1) neutral (white), and one (1) equipment ground (green).
Verify the electrical requirements of each unit from the Data Plate located on the mechanical compartment (see
page 9). Each oven requires a separate
20-amp
breaker to be shut off for service and maintenance. Label
both breakers if a double stack configuration is installed. An electrical wiring diagram is located inside the
control box cover. We recommend that the gas and electric utilities be installed and in place well before the
oven(s) arrive.
Electrical Supply (U.S. and Canada)
(UNITS WITH PUSH BUTTON CONTROL BOARD)
Single Phase (Standard)
Lincoln X-2 ovens that are configured to operate on single-phase power will require a 20 amp single phase,
230VAC, two wire with ground, 60 Hz service: Two (2) “hot” or current carrying leads (red and black) and one
(1) equipment ground (green).
Three Phase (Optional)
Lincoln X-2 ovens that are configured to operate on three-phase power will require a 20 amp three phase,
230 VAC, three wire with ground, 60 Hz service: Three (3) “hot” or current carrying leads (red, blue & black) and
one (1) equipment ground (green).
Verify the electrical requirements of each unit from the Data Plate located on the mechanical
compartment (see page 9). Each oven requires a separate
20-amp
breaker to be shut off for service and
maintenance. Label both breakers if a double stack configuration is installed. An electrical wiring
diagram is located inside the control box cover. We recommend that the gas and electric utilities be
installed and in place well before the oven(s) arrive.
For all other countries:
Single Phase: 230 VAC; one hot, one neutral & one ground
Three Phase: 230/415 VAC; three hot, one neutral & one ground
Содержание Impinger 3262BWEC
Страница 6: ...Impinger X2 Operator Manual 6...
Страница 7: ...Impinger X2 Operator Manual 7...
Страница 8: ...Impinger X2 Operator Manual 8 FIGURE A Rev 4 05...
Страница 34: ...Impinger X2 Operator Manual 34 LABEL DEFINITIONS...
Страница 35: ...Impinger X2 Operator Manual 35 SCHEMATIC UNITED STATES CANADA MODELS WITH PUSH BUTTON CONTROL BOARD...
Страница 36: ...Impinger X2 Operator Manual 36 SCHEMATIC DIAGRAM MODELS 3262 2 3270 2 50 HZ WITH PUSH BUTTON CONTROLS...
Страница 41: ...9432 ELECTRIC UTILITY KIT UTILITY EXTENSION KIT INSTALLATION INSTRUCTIONS...
Страница 46: ...This page intentionally left blank...
Страница 47: ...Impinger X2 Operator Manual 47 9431 GAS UTILITY KIT UTILITY EXTENSION KIT INSTALLATION INSTRUCTIONS...
Страница 52: ...Impinger X2 Operator Manual 52...