ES58 • EM58 MODBUS®
Response PDU
Function code
1 byte
03 hex
Byte count
1 byte
2 x
N*
Register value
N*
x 2 bytes
*N = Quantity of registers
Exception Response PDU
Error code
1 byte
83 hex (=03 hex + 80 hex)
Exception code
1 byte
01 or 02 or 03 or 04
Here is an example of a request to read the
parameter (registers 5 and 6).
Request
Response
Field name
(Hex)
Field name
(Hex)
Function
03
Function
03
Starting address Hi
00
Byte count
04
Starting address Lo
04
Register 5 value Hi
00
No. of registers Hi
00
Register 5 value Lo
00
No. of registers Lo
02
Register 6 value Hi
05
Register 6 value Lo
DC
(registers 5 and 6) contains the value 00 00 hex and 05 DC hex, i.e. 1500 in
decimal notation.
MAN ESx58x_EMx58x MB E 1.3