ES58 • EM58 MODBUS®
The DIP switches are located just beneath.
Figure 3: DIP switches
4.5.1 Setting data transmission rate: Baud rate and Parity bit (Figure 3)
WARNING
Power supply must be turned off before performing this operation!
Use the DIP switch A to set the data transmission rate (baud rate and parity bit).
Set the binary value of the baud rate and the parity bit according to the
following table, considering that: ON = 1; OFF = 0.
Switch
Baud rate
Parity bit
0000
9600 bit/s
No parity
1000
9600 bit/s
Even
0100
9600 bit/s
Odd
1100
19200 bit/s
No parity
0010 (default)
19200 bit/s
Even
1010
19200 bit/s
Odd
0110
115200 bit/s
No parity
1110
115200 bit/s
Even
0001
115200 bit/s
Odd
MAN ESx58x_EMx58x MB E 1.3