SMAL CANlift
MAN SMAL I6 E 1.3.doc
Pag.16
www.lika.it
www.lika.biz
1906
PDO1 parameters
PDO1 is used by default for cyclic transmission of the position value.
See object 1906h sub 5 for setting of cyclic timer.
•
01
COB;ID of PDO1 [Unsigned32, rw]
Default = 0000 018Ch
•
02
Transmission type [Unsigned8, rw]
Default = FFh (cyclic transmission)
•
03
Inhibit time [Unsigned8, rw]
Default = 00h
•
04
Reserved
•
05
Event Timer
Default = 00h (disabled)
ATTENTION:
The COB;ID of PDO1 for CANlift devices follows the lift number and the car
position unit. If more devices are connected to the network with the same lift
number, be sure to set different COB;ID of PDO1 for each device.
NOTE:
•
The transmission of PDO1 can be enabled (or disabled) setting to “0” (or “1”)
the most significant bit (MSB) used by PDO (object 1906h, sub1).
0000 018Ch: PDO1 enable
8000 018Ch: PDO1 disabled.
•
Cyclic transmission or synchronous transmission can be modified setting the
object 1906h sub 2:
01h: synchronous transmission each SYNC;
02h: synchronous transmission after 2 SYNC;
…
FEh: cyclic transmission (see object 3007h for cyclic timer)
FFh: cyclic transmission (see object 1906h sub 5 for cyclic timer)
1B0601
PDO1 mapping parameter [Unsig32, rw]
This object contains the mapped position value of the encoder according to the
DSP417 device profile.
Default = 6383 0120h