Lighthouse REMOTE 2014P, 3014P, 5014P Operating Manual
A-10
248083408-1 Rev 1
Enable Alarming for a Channel
To enable alarming on the third particle channel, the user would enable
Bit 1 for register 43014.
To disable alarming on the third channel and enable alarming on the
second channel, disable Bit 1 for register 43014 and enable Bit 1 for
register 43012.
To disable alarming completely, disable Bit 1 for register 43012. Now,
no channels are enabled for alarms.
Use the Threshold registers to set the alarm threshold value. This is
described in the next section.
43041
unsigned int
Enable for Analog Channel 1 [high]
43042
unsigned int
Enable for Analog Channel 1 [low]
43043
unsigned int
Enable for Analog Channel 2 [high]
43044
unsigned int
Enable for Analog Channel 2 [low]
43045
unsigned int
Enable for Analog Channel 3 [high]
43046
unsigned int
Enable for Analog Channel 3 [low]
43047
unsigned int
Enable for Analog Channel 4 [high]
43048
unsigned int
Enable for Analog Channel 4 [low]
Table A-9 Alarm Enable Registers
Register Data
Type
Description
Table A-10 Example of Alarming on Channel 2
Registers
Particle
Channel
Bit 1
Enabled
43009 - 43010
1
0
43011 - 43012
2
1
43013 - 43014
3
0
43015 - 43016
4
0
43017 - 43018
5
0
43019 - 43020
6
0
Содержание Remote 2014P
Страница 1: ......
Страница 2: ......
Страница 6: ......
Страница 10: ...Lighthouse REMOTE 2014P 3014P 5014P Operating Manual t iv 248083408 1 Rev 1...
Страница 12: ...Lighthouse REMOTE 2014P 3014P 5014P Operating Manual ii 248083408 1 Rev 1...
Страница 14: ...Lighthouse REMOTE 2014P 3014P 5014P Operating Manual 1 2 248083408 1 Rev 1...
Страница 20: ...Lighthouse REMOTE 2014P 3014P 5014P Operating Manual 2 6 248083408 1 Rev 1...
Страница 40: ...Lighthouse REMOTE 2014P 3014P 5014P Operating Manual 3 20 248083408 1 Rev 1...
Страница 72: ...Lighthouse REMOTE 2014P 3014P 5014P Operating Manual B 2 248083408 1 Rev 1...
Страница 74: ...Lighthouse REMOTE 2014P 3014P 5014P Operating Manual C 2 248083408 1 Rev 1...
Страница 79: ......
Страница 80: ......