54 Operation
LAN Interface Shutdown
Initiated
This alarm indicates the LAN is being
shut down for a programmed action
due to the activation of one or more
alarms.
This should activate the automatic
shutdown sequence programmed
into your LAN operating system.
Load on Manual Bypass
The Maintenance Bypass switch is in
the Maintenance position.
When the maintenance activity has
been completed, return the unit to
normal operation.
Logic Error
Automatic diagnostic testing has
detected a failure (of hardware or
software) in the UPS internal control
system. A second message may
indicate internal test or software
time-out. The load has been
automatically transferred to bypass.
Record the alarm condition and
contact Liebert Global Services.
Low Battery Shutdown
Battery has discharged to the
minimum allowable voltage. If the
bypass is available the unit will
transfer to bypass. If the bypass is
not available, the UPS is shut down.
No power is being supplied to the
critical load.
When the battery has recharged and
if there is not fault, the unit will
retransfer from bypass. If bypass
was not available, when input power
becomes available, perform a UPS
start-up procedure. Unit will start-up
by itself if auto-restart is enabled.
Low Battery Warning Issued
The battery voltage measurement
has reached the user-programmed
warning value. The unit will shut
down at the specified time if input
power is not restored.
User should take appropriate
measures to insure an orderly
shutdown of the system. If the user
has set the warning level above 2
minutes, you may also take action to
shed load and increase battery time
to complete discharge.
Manual Off Activated
(Alarm History Only)
The UPS has been shut down
remotely through the RS-232
interface or through the advanced
configuration menu.
To restart the UPS follow the
procedures in 3.0 - Operation.
Manual On Activated
(Alarm History Only)
The UPS has been turned on
remotely through the RS-232
interface or through the advanced
configuration menu.
This is an information alarm only.
Make sure it is OK that the UPS is
energized.
Manual Transfer-to-Bypass
Activated
(Alarm History only)
The UPS has been transferred to
bypass remotely through the RS-232
interface or through the advanced
configuration menu. The UPS stays
on Bypass until the retransfer is
activated and all required conditions
for retransfer are satisfied.
Determine why the UPS was
transferred to bypass. Clear the fault
or problem and retransfer to normal
operation. If the problem cannot be
corrected, contact Liebert Global
Services.
Memory Failure ROM or
Memory Failure RAM
The microprocessor has failed a self
diagnostic test during the start-up
process. Start up will not be allowed.
Contact Liebert Global Services.
Neutral SCR Short
On units equipped with the isolated
neutral option, the SCR that transfers
the neutral has failed short.
Contact Liebert Global Services.
Non Volatile Ram U88
Corrupted
Non Volatile ram has a long life
(10 year) back up battery, either the
battery is near end or life or the
memory has been corrupted.
Contact Liebert Global Services.
Non Volatile Ram U88 Failed
Non Volatile ram back up battery has
reached end of life or the Main
control board memory has had a
failure.
Contact Liebert Global Services.
Table 5
Alarm Messages (continued)
Alarm Message
Meaning
Corrective Action
Содержание UPStation S3
Страница 1: ...POWER PROTECTION UPStation S3 Three Phase 12 kVA to 24 kVA 50 and 60 Hz User Manual ...
Страница 2: ......
Страница 6: ...iv ...
Страница 23: ...Installation 17 Figure 1 One Line Drawing Single Input Configuration 200 240V In Out ...
Страница 24: ...18 Installation Figure 2 One Line Drawing Dual Input Configuration 200 240V In Out ...
Страница 25: ...Installation 19 Figure 3 One Line Drawing Single Input Configuration With Neutral Isolation 200 240V In Out ...
Страница 26: ...20 Installation Figure 4 One Line Drawing Dual Input Configuration With Neutral Isolation 200 240V In Out ...
Страница 27: ...Installation 21 Figure 5 One Line Drawing Single Input Configuration 400 480 600V In 208V Out ...
Страница 28: ...22 Installation Figure 6 One Line Drawing Dual Input Configuration 400 480 600V In 208V Out ...
Страница 31: ...Installation 25 Figure 9 One Line Drawing Single Input Configuration 400 480 600V In Out ...
Страница 32: ...26 Installation Figure 10 One Line Drawing Dual Input Configuration 400 480 600V In Out ...
Страница 34: ...28 Installation Figure 12 One Line Drawing Dual Input Configuration With Neutral Isolation 400 480 600V In Out ...
Страница 35: ...Installation 29 Figure 13 Cabinet Dimensions ...
Страница 36: ...30 Installation Figure 14 Cabinet Dimensions With Transformer Cabinet ...
Страница 37: ...Installation 31 Figure 15 Connecting Terminal Details ...
Страница 38: ...32 Installation Figure 16 Connecting Terminal Details With Transformer Cabinet ...
Страница 39: ...Installation 33 Figure 17 Battery Option Details 12 Inch Cabinet ...
Страница 40: ...34 Installation Figure 18 Battery Option Details 24 Inch Cabinet ...
Страница 41: ...Installation 35 Figure 19 Field Lug Wiring Terminations ...
Страница 42: ...36 Installation Figure 20 Unloading Instructions ...
Страница 43: ...Installation 37 Figure 21 Unloading Instructions 24 Inch Battery Cabinet ...
Страница 44: ...38 Installation Figure 22 Battery Times ...
Страница 53: ...Operation 47 Figure 25 Configuration Menu Tree ...
Страница 55: ...Operation 49 Figure 26 Control Switch Locations ...
Страница 68: ...62 Features Options Figure 27 RS 232 Connections ...
Страница 69: ...Features Options 63 Figure 28 Output Distribution Panel Board ...